38(44)
meanwhile for 3 seconds till F-06 displays in PV..
2) Press
to set SV into 0003 and press
“
Enter
”
, at this time F-06 displays
in PV.
3) Now pressing
can alter value, press
“
Enter
”
to input after confirming
then jump to F-07.
4) If you want to leave the function setting, just press
“
SET
”
.
1. F-06 stands for the passwords of second level.
2. F-07 stands for proportional band of heating side (P); it is a preset value
before delivery.
3. F-08 stands for integration time of heating side (I); it is a preset value
before delivery.
4. F-09 stands for differential time of heating side (D); it is a preset value
before delivery.
5. F-10 stands for switch cycle of heating side; its preset value is 15 sec.
6. F-16 stands for power deliver delay time of heater, it is adjustable, the unit
is sec. (Heater begins to work after the blower starts the delay time
setting.)
7. F-17 stands for blower power-off delay time, it is adjustable, the unit is sec..
(Press the
“
ON/OFF
”
key and the heater stops, the blower stops after the
delay time to avoid abnormal condition caused by high temperature.)
8. F-18 stands for the protection of maximum temperature. Its setting range is
140~250. (When the drying temperature value is high than the system
setting one, the machine stops and give an alarm to avoid overheating
caused by other faults.)
9. F-19 stands for micro switch time setting of honeycomb rotor.
“
OFF
”
functions as shut-off and
“
ON
”
functions as open. The setting range is
0~9999 with the unit is sec.. (Rotor detecting time, when the setting time is
less than the time for the rotor rotate once, the micro switch periodic resets
and detect whether the honeycomb is rotating.)