Setting Functions (continued)

Instructions to set functions are as follows:
1. Press the FUN button; the display will indicate:

NOTE: The display will always show what operating

mode is set (mode -01- in this example) and what

function (1) is being displayed.

2. Use the lower keys to set secondary high and low

limits  (follow  the  same  instructions  listed  under

“Setting High and Low Limits” section on page 7).

3. Press the FUN button; the display will reflect:

Function 2 is now showing on the primary display

(factory setting).

4. Use the NUMERIC buttons to set the hysteresis of

the upper and lower limits.

5. Press the FUN button; the display will show:

Function 3 is being reflected on the primary display

(factory setting).

6. Use  any  of  the  lower  buttons  to  toggle  between

securing and not securing (see tables on page 11)

the primary high and low settings.

7. Press the FUN button; the display will reflect:

Function 4 is now showing (factory setting).
NOTE: This function is mainly used with mode -01-

only.

8. Use the NUMERIC buttons to set the output activation

of any set limit.

9. Press the FUN button, the display will show:

Function 5 is now showing (factory setting).

Memory  Feature

The  function  of  the  MEM  button  is  to  aid  the

DT-5TXR/DT-5TS to  memorize and display through the

secondary displays the maximum and minimum value of

the  main  display  for  as  long  as  it  has  been  activated.

Simply  activate  the  MEM  button  by  pushing  it

momentarily. The lower left secondary display will reflect

the maximum value of the main display and the lower

right secondary display will reflect the minimum value of

the main display. Also a small LED will begin to flash.

To de-activate the memory feature, simply push the MEM

button  again.  The  LED  under  it  will  stop  flashing  and

the secondary displays will return to their previous state.

10. Use  any  of  the  lower  buttons  to  toggle  between

the three settings (see tables on page 11) for what

the secondary displays (A and B) will show.

11. Press the FUN button; the display will reflect:

Function 6 is now showing (factory setting).

12. Use the NUMERIC buttons to enter the number at

which the primary display should read zero.
For example: if it is desired for the display to read

zero  when  the  RPM  drops  below  600,  then  6  0  0

should be entered.

13. Press the FUN button; the display will show:

Parameter 7 is now showing (factory setting).

14. Use any of the lower buttons to scroll between the

three types of averaging (see tables on page 11) for

an unstable sensor.  The number of times that the

meter will average the frequency is directly related

to the update time chosen (parameter 4).

15. Press the FUN button; the display will reflect:

Parameter 8 is now showing (factory setting).

16. Use the lower keys to toggle between either having

the deceleration to zero value “on” or “off” (see tables

on page 11).

17. Press the SET button to store the function settings

and exit.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DT-5TS

Page 1: ...Instruction Manual DT 5TXR DT 5TS DIGITAL PANEL MOUNT TACHOMETER www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 2: ...rtant Safety Precautions 3 Display and Keypad 4 Rear Panel and Terminals 5 Set Up 5 Power 5 Sensor Connection 5 Self Test 5 Panel Installation 6 Factory Settings 6 Parameter Settings 6 Function Settin...

Page 3: ...g while saving time Accepts modules DT 5TXR only which provide different types of outputs i e analog voltage analog current 4 20 mA relay closures set points BCD output and others for recording purpos...

Page 4: ...a r a p s t e S n o t t u B t e S 7 n o i t c e l e s e d o M n o t t u B e d o M 8 l a c e d r o f a e r A l a c e D t i n U 9 t n e m e r u s a e m f o s t i n u s y a l p s i D y a l p s i D y r a...

Page 5: ...nts etc 4 When satisfied that all LED s are operational press the SET button to exit SENSOR TYPE TERMINAL NUMBER FREQUENCY or RPMRANGE OPERATION TEMPERATURE FILTER M P R 0 0 0 5 0 C 0 6 B 1 E R 3 0 C...

Page 6: ...1 000 RPM 3 Display units 1000 1 000 4 Update time _ 1 0 _ 1 second 5 Display Hold after input signal ceases _ _006 0 6 seconds 6 Input filter _ 10 _ 10 kHz DEFAULT FACTORY SETTING PARAMETER DESCRIPT...

Page 7: ...ogrammed into the DT 5TXR DT 5TS In addition there are also function settings to further customize the DT 5TXR DT 5TS NOTE Because the flow rate measurement mode 04 is only used in the Japanese market...

Page 8: ...feet per minute and the belt that is being measured is moving at a rate of 55 5 f min then 5 5 5 would have to be entered and the negative decimal point button pressed once If the desired reading is R...

Page 9: ...Press the PAR button 8 Use any of the lower buttons to scroll through see table above and select an update time 9 Press the PAR button 10 Use the NUMERIC buttons to enter the time in seconds that the...

Page 10: ...e meter will then use this number to set parameters 1 and 2 Set the teaching feature as follows 1 Determine the output RPM 2 Confirm that the meter is receiving a signal from the sensor the SIG indica...

Page 11: ...e r e t s y H 2 _ __ _ 0 0 0 3 Secures the 1st high and 1st low setting 0 not secured 1 secured _ 0 _ Notsecured d n o c e s 9 9 0 t i m i l t e s y n a f o n o i t a v i t c a t u p t u O 4 _ __ _ 0...

Page 12: ...activate the MEM button by pushing it momentarily The lower left secondary display will reflect the maximum value of the main display and the lower right secondary display will reflect the minimum val...

Page 13: ...nd the operator wants to observe the changes in this case higher update times are selected or if the speed changes rapidly within certain limits this may bother the observer a lower update time is sel...

Page 14: ...DT 5TS has a MODE for this application and similar ones where it can measure the ON time of a signal that starts when the process begins until it ends see signal waveform diagram top right NOTE The di...

Page 15: ...20mA DOP CPTR Relay output HI GO LO 3 C type relays DOP TRTR NPN OC output H 1 H 2 GO L 1 L 2 and ZERO DOP RMTR Ratio of two input functions Lower Connector Options with Connectors C DOP FVC Analog ou...

Page 16: ...OP FVC module coupled with the DT 5TXR panel meter provides three popular voltage outputs and one current output for recording purposes and PLC applications The voltages are a 0 to 10 VDC b 1 to 5 VDC...

Page 17: ...ll be approximately 10 msec 1 indicates that the update time will correspond with the display update time already chosen see Setting Mode Parameters 4 7 Press the FUN button display will reflect The d...

Page 18: ...Module DT 5TXR BCD The model DT 5TXR BCD combination satisfies PCs and PLCs that require a BCD parallel signal The DOP BCD module can be configured with a negative logic output 0 HI and 1 LO or a posi...

Page 19: ...ncy 30 kHz 0 999999 with selectabledecimal point 0 008 1 digit DT 5TXR Display Range MODEL Mode r e t e M e t a R r e t e m o h c a T Elapsed Time Process Time 0 00 00 9 59 59 0 00 00 0 59 59 or or 0...

Page 20: ...NIFICATION LIMITATION OF DAMAGES Buyer agrees to indemnify and hold Shimpo Instruments harmless from and against all claims and damages imposed upon or incurred arising directly or indirectly from Buy...

Reviews: