Mode -01- (RPM or Rate Measurement) continued

Set the parameters in mode -01- as follows:
1. Press the PAR button; the display will indicate:

The “-01- P01” on secondary display A indicates that

the meter is in the RPM mode (-01-) and parameter 1

is  showing  on  the  primary  display  (1  ppr  [factory

setting]).

2. Using the NUMERIC buttons, enter the number of

pulses per revolution produced by the sensor being

used  (1-9999).  For  example,  if  a  rotary  pulse

generator has an output of 60 ppr, then 6 0 would

have to be entered.

3. Press the PAR button; the display will reflect:

The  secondary  display  A  reflects  that  the  meter  is

still in mode -01-, but parameter 2 is showing on the

primary display (1000 RPM [factory setting]).

4. Using the NUMERIC buttons, enter the number of

RPM  that  must  be  monitored  (up  to  99999).  For

example, if the motor to be monitored has a speed

of 1,750 RPM, then 1 7 5 0 would have to be entered.

5. Press the PAR button; the display will show:

As the secondary display indicates, parameter 3 is

reflected  on  the  primary  display  (1000  [factory

setting]).

6. Use the NUMERIC buttons to enter the value of the

display as it relates to the already programmed RPM

setting.  For example: if the desired display reading

is feet per minute and the belt that is being measured

is moving at a rate of 55.5 f/min, then 5 5 5 would

have to be entered and the negative/decimal point

button pressed once.  If the desired reading is RPM,

then the same 1 7 5 0 would have to be entered.

7. Press the PAR button; the display will reflect:

Parameter 4 is now showing on the primary display

(1.0 second [factory setting]).

8. Use any of the lower buttons to scroll through the

update  times  (see  table  under  “Setting  Mode

Parameters” on page 7) until the desired reading is

displayed.

9. Press the PAR button, the display will indicate:

The primary display is now reflecting parameter 5

(6 sec [factory setting]).

10. Press  the  NUMERIC  buttons  to  enter  the  value  in

seconds that the display should hold the final reading

after the input signal ceases.

11. Press the PAR button; the display will reflect:

Parameter 6 is showing on the primary display (10

kHz [factory setting]).

12. Refer  to  the  “Connection  of  Sensors”  chart  under

the  “Set-Up”  section  for  the  proper  filter  for  the

sensor being used.  Press any of the lower buttons

to scroll through the input filters (see table under

“Setting  Mode  Parameters”  on  page  7)  until  the

desired reading is showing.

13. Press the SET button to store the parameter settings

and exit.

NOTE: Please see page 13 for an example of MODE -01-

operation.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DT-5TS

Page 1: ...Instruction Manual DT 5TXR DT 5TS DIGITAL PANEL MOUNT TACHOMETER www GlobalTestSupply com Find Quality Products Online at sales GlobalTestSupply com...

Page 2: ...rtant Safety Precautions 3 Display and Keypad 4 Rear Panel and Terminals 5 Set Up 5 Power 5 Sensor Connection 5 Self Test 5 Panel Installation 6 Factory Settings 6 Parameter Settings 6 Function Settin...

Page 3: ...g while saving time Accepts modules DT 5TXR only which provide different types of outputs i e analog voltage analog current 4 20 mA relay closures set points BCD output and others for recording purpos...

Page 4: ...a r a p s t e S n o t t u B t e S 7 n o i t c e l e s e d o M n o t t u B e d o M 8 l a c e d r o f a e r A l a c e D t i n U 9 t n e m e r u s a e m f o s t i n u s y a l p s i D y a l p s i D y r a...

Page 5: ...nts etc 4 When satisfied that all LED s are operational press the SET button to exit SENSOR TYPE TERMINAL NUMBER FREQUENCY or RPMRANGE OPERATION TEMPERATURE FILTER M P R 0 0 0 5 0 C 0 6 B 1 E R 3 0 C...

Page 6: ...1 000 RPM 3 Display units 1000 1 000 4 Update time _ 1 0 _ 1 second 5 Display Hold after input signal ceases _ _006 0 6 seconds 6 Input filter _ 10 _ 10 kHz DEFAULT FACTORY SETTING PARAMETER DESCRIPT...

Page 7: ...ogrammed into the DT 5TXR DT 5TS In addition there are also function settings to further customize the DT 5TXR DT 5TS NOTE Because the flow rate measurement mode 04 is only used in the Japanese market...

Page 8: ...feet per minute and the belt that is being measured is moving at a rate of 55 5 f min then 5 5 5 would have to be entered and the negative decimal point button pressed once If the desired reading is R...

Page 9: ...Press the PAR button 8 Use any of the lower buttons to scroll through see table above and select an update time 9 Press the PAR button 10 Use the NUMERIC buttons to enter the time in seconds that the...

Page 10: ...e meter will then use this number to set parameters 1 and 2 Set the teaching feature as follows 1 Determine the output RPM 2 Confirm that the meter is receiving a signal from the sensor the SIG indica...

Page 11: ...e r e t s y H 2 _ __ _ 0 0 0 3 Secures the 1st high and 1st low setting 0 not secured 1 secured _ 0 _ Notsecured d n o c e s 9 9 0 t i m i l t e s y n a f o n o i t a v i t c a t u p t u O 4 _ __ _ 0...

Page 12: ...activate the MEM button by pushing it momentarily The lower left secondary display will reflect the maximum value of the main display and the lower right secondary display will reflect the minimum val...

Page 13: ...nd the operator wants to observe the changes in this case higher update times are selected or if the speed changes rapidly within certain limits this may bother the observer a lower update time is sel...

Page 14: ...DT 5TS has a MODE for this application and similar ones where it can measure the ON time of a signal that starts when the process begins until it ends see signal waveform diagram top right NOTE The di...

Page 15: ...20mA DOP CPTR Relay output HI GO LO 3 C type relays DOP TRTR NPN OC output H 1 H 2 GO L 1 L 2 and ZERO DOP RMTR Ratio of two input functions Lower Connector Options with Connectors C DOP FVC Analog ou...

Page 16: ...OP FVC module coupled with the DT 5TXR panel meter provides three popular voltage outputs and one current output for recording purposes and PLC applications The voltages are a 0 to 10 VDC b 1 to 5 VDC...

Page 17: ...ll be approximately 10 msec 1 indicates that the update time will correspond with the display update time already chosen see Setting Mode Parameters 4 7 Press the FUN button display will reflect The d...

Page 18: ...Module DT 5TXR BCD The model DT 5TXR BCD combination satisfies PCs and PLCs that require a BCD parallel signal The DOP BCD module can be configured with a negative logic output 0 HI and 1 LO or a posi...

Page 19: ...ncy 30 kHz 0 999999 with selectabledecimal point 0 008 1 digit DT 5TXR Display Range MODEL Mode r e t e M e t a R r e t e m o h c a T Elapsed Time Process Time 0 00 00 9 59 59 0 00 00 0 59 59 or or 0...

Page 20: ...NIFICATION LIMITATION OF DAMAGES Buyer agrees to indemnify and hold Shimpo Instruments harmless from and against all claims and damages imposed upon or incurred arising directly or indirectly from Buy...

Reviews: