DIGITAL WEIGHING INDICATOR
SI 4500
- 52 -
6-6. Serial Interface (option 04 : RS-232C/422/485)
RS-422/485 serial interface is more stable for electric noise effect compare with other communication
method, using electric current difference.
But, install isolated place from Power cable or other electric cables and wires, and please use shielded
cable for better performance.
Recommendable communication distance is about 1.2km.
If you install additional RS-232C interface, please refer “6-1. Serial Interface” section.
6-6-1. Signal Format
①
. Type : RS-422/485
②
. Format : Baud Rate : Refer “F-function 31”.
Data Bit : 7 or 8(No Parity)
Stop : 1
Parity Bit : Even, Odd, No Parity (Selectable)
Code : ASCII (STX 02H, ETX 03H, CR 0DH, LF 0AH)
1
LSB
0
1
2
3
4
5
MSB
6
0
6-6-2. Data Format
Same as RS-232C (Refer “6-1. Serial Interface”)
6-6-3. RS-422 Circuit (In case of RS-485, Use No6 and 7 pin - No.8 and 9 will be use)
Start 1 Bit
Data Bit
Parity Bit
Stop 1 Bit
1.5V Electric
Potential Difference