MOVITRAC
®
series 0500
General electronic data
Speed setpoints
X1:1
Reference voltage for setpoint potentiometer: +10 V
DC
± 2%
Current rating I
max
= 15 mA, short-circuit proof
Reference potential X1:7 or X1:11
External setpoint inputs
X1:2
(selectable via jumpers J1 / J2)
n = 0...+10 V / 2...10 V
R
i
= 100 k
Ω
resolution: 10 bit
Linearity < 2% in the range of 0...10 V
sample time: 8.2 ms
n = 0...20 mA / 4...20 mA
R
i
= 500
Ω
Frequency ramp generator time range
Acceleration ramp and deceleration ramp separately adjustable
Range: 0.10...999.00Hz/s
STOP ramp adjustable, range: 0.00...999.00 Hz/s
Binary inputs
Input mode
Control functions
X1:3 <STR>
X1:4 <STL>
X1:5 <S1IND>
X1:6 <S2IND>
Input voltage = 0...30 V
R
i
= 4.7 k
Ω
sample time
≤
8.2 ms
Reference potential X1:7 or X1:11 electrically isolated by optocouplers
(+ 8...30) V = “1“ = contact closed
(0...+ 2) V = “0“ = contact open
Start CW
Start CCW
Fixed frequency 1/ 2/ 3 (3 fixed frequencies) programmable
Binary outputs
X1:8
OUT
X1:9
OUT
open collector
low active
electrically isolated by optocouplers
V
max
= 30 V
R
i
= 100
Ω
Current rating I
max
= 50 mA
Important: not short-circuit proof, not external-voltage-proof
Reference potential: ground X1:7 or X1:11
Programmable:
collective fault / output voltage / CW / CCW / motor standstill / setpoint
reached / frequency limit FF5 exceeded / current limit / brake chopper
active / unit shutdown on faults
Output
X1:10
analog
(selectable via jumpers J3 / J4)
digital
Analog output signal: (0...+10 V) x (0...200%)
tolerance
±
2%
Current rating I
max
= 2 mA
R
i
= 100
Ω
resolution: 10 bit
Important: not short-circuit-proof, not external-voltage-proof
programmable: output frequency / apparent current / active current /
active power
PWM or binary signal
Open collector
V
max
= 15 V
Current rating
I
max
= 15 mA
R
i
= 100 W
resolution: < 0.3 Hz
Important: not short-circuit-proof, not external-voltage-proof
Programmable: output frequency / brake chopper active
Reference terminals
1:7, X1:11
Reference potential for X1:1, X1:2-X1:6 and X1:8-X1:10
PTC input
X5: - / PTC
PTC = PTC thermistor = TF thermistor in motor
non-isolated (referred to supply potential)
R
PTC thermistor
at rated response temperature > 3 k
Ω
(DIN 44081)
Recommendation: TF.. PTC thermistors
If no PTC thermistor is used, terminals X5/- and X5/PTC must be
jumpered.
6
Technical Data
24
MOVITRAC
®
0500 - Operating Instructions