The FBG 01 keypad indicates the faults the same as the basic unit, and in addition signals the
following faults:
Code
Meaning
In fault memory
VAL 95 ERR1
Operating errors
ATT1
Parameter adjustment not allowed while motor is running
ATT2
Manual operation via FBG 01 keypad not allowed if motor is already running
ATT3
Access to ParaCard PAC 01 not allowed while motor is running
ATT4
System in fault condition; manual operation via FBG 01 not allowed
ATT5
Motor data must be complete for selected function
(e.g. for 48 IxR compensation)
ERROR
Invalid password
Errors ParaCard PAC 01
ERR91
PAC 01 write-protected
ERR92
Plausibility check error
ERR93
Unable to read PAC 01, wrong inverter type
ERR94
Unable to read PAC 01, parameter data not compatible
ERR96
Connection to PAC 01 interrupted
ERR97
PAC 01 invalid (CS test)
Inverter faults
E-CPU
Fault in processor pcb (AUTOSTART in 72 START causes reset)
1
E-OFF
Undervoltage (no entry in fault memory)
E-OC
Overcurrent/short-circuit after power up, earth circuit
3
E-OV
Overvoltage
4
E-OLM
Ixt motor
5
E-OLI
Ixt inverter
6
E-OTM
Overtemperature motor (only with PTC thermistor connection)
7
E-OTI
Inverter overtemperature
8
E-EEP
EEPROM fault
9
E-PWR
Power section not recognized
10
5.4
SEW Electronics Service
If a fault cannot be reset, then please contact the SEW Electronics Service
(
→
“After-Sales and Spare Parts Service”).
If you return equipment for repair, please:
- describe the nature and extent of the fault
- explain when and under what background conditions the fault occurred
- state the suspected cause
- state any abnormal circumstances, etc. that may have preceded the fault.