background image

The FBG 01 keypad indicates the faults the same as the basic unit, and in addition signals the
following faults:

Code

Meaning

In fault memory
VAL 95 ERR1

Operating errors

ATT1

Parameter adjustment not allowed while motor is running

ATT2

Manual operation via FBG 01 keypad not allowed if motor is already running

ATT3

Access to ParaCard PAC 01 not allowed while motor is running

ATT4

System in fault condition; manual operation via FBG 01 not allowed

ATT5

Motor data must be complete for selected function
(e.g. for 48 IxR compensation)

ERROR

Invalid password

Errors ParaCard PAC 01

ERR91

PAC 01 write-protected

ERR92

Plausibility check error

ERR93

Unable to read PAC 01, wrong inverter type

ERR94

Unable to read PAC 01, parameter data not compatible

ERR96

Connection to PAC 01 interrupted

ERR97

PAC 01 invalid (CS test)

Inverter faults

E-CPU

Fault in processor pcb (AUTOSTART in 72 START causes reset)

1

E-OFF

Undervoltage (no entry in fault memory)

E-OC

Overcurrent/short-circuit after power up, earth circuit

3

E-OV

Overvoltage

4

E-OLM

Ixt motor

5

E-OLI

Ixt inverter

6

E-OTM

Overtemperature motor (only with PTC thermistor connection)

7

E-OTI

Inverter overtemperature

8

E-EEP

EEPROM fault

9

E-PWR

Power section not recognized

10

5.4

SEW Electronics Service

If a fault cannot be reset, then please contact the SEW Electronics Service
(

“After-Sales and Spare Parts Service”).

If you return equipment for repair, please:
- describe the nature and extent of the fault
- explain when and under what background conditions the fault occurred
- state the suspected cause
- state any abnormal circumstances, etc. that may have preceded the fault.

5

Operation and Service

22

MOVITRAC

®

0500 - Operating Instructions

Summary of Contents for MOVITRAC 0500

Page 1: ...MOVITRAC 0500 Frequency Inverters Operating Instructions Edition 01 97 0922 3916 0197...

Page 2: ...underneath terminal strip X1 8 Terminal strip X1 electronic control connections 9 Terminal strip X5 power section Terminal strips X1 and X5 are included with the unit they are placed on the unit and s...

Page 3: ...ed potentiometer 15 4 3 Setting the signal mode for FSINA and SOUTA 16 4 4 Complete parameter list 17 4 4 1 Menu branch VAL display parameters 17 4 4 2 Menu branch PARA adjustable parameters 18 5 Oper...

Page 4: ...rves the right to make alterations to the technical data and design which serve the cause of technical progress Storage instructions Permissible storage temperature 25 C 70 C Permissible humidity No r...

Page 5: ...mpliance with EMC regulations Sec 3 2 with EMC Directive 89 336 EEC Type designation Example MOVITRAC 0504 231 1 00 Version 00 standard Quadrants 1 1 quadrant Type of supply 1 single phase Rated suppl...

Page 6: ...ng displays H1 and H2 or any of the other status indicators go out this does not mean that the inverter is disconnected from the supply and is de energized Protective measures and equipment must be ch...

Page 7: ...inverter is inhibited Only an inductive resistive load motor may be connected at the inverter output no capacitive load For jogging use the commands clockwise STR counterclockwise STL The mains conta...

Page 8: ...1 input filter MOVITRAC 0508 231 1 00 NF008 231 input filter Mount the NF input filter close to the corresponding MOVITRAC 0500 but outside the minimum ventilation space required Keep the connecting l...

Page 9: ...t limit Imax 50 mA 9 brake chopper active 10 disconnection on faults 10 SOUTA Analog binary output Imax 2 mA analog Imax 15 mA binary Important not short circuit proof do not apply external source vol...

Page 10: ...e control an external 24 V supply is necessary The binary output drives an external brake relay K1 24 V 1 2 W max 50 mA This relay controls the brake via a brake contactor K2 The brake must be actuate...

Page 11: ...the supply 5 Start the drive in the direction of rotation you require X1 3 STR or X1 4 STL 1 The drive will start if setpoint input 0 1 V 0 5 Hz or one of the fixed setpoints is selected Important if...

Page 12: ...urn 4 Labelling field for bar graph display 5 Arrow key up 6 Key Start Enter 7 Optional ParaCard PAC 01 8 Connecting cable FBG 01 inverter 9 Dimension for bar graph display 10 5 digit actual value and...

Page 13: ...menu branches or parameters Cancels changes The menu is structured as follows VAL display values PARA adjustable parameters In parameter 01 MODE operating mode three operating modes can be selected T...

Page 14: ...changed when the inverter is inhibited When the unit is enabled and started the parameters can only be read Adjustable parameters Sec 4 4 2 Manual operation can only be selected if the unit is inhibi...

Page 15: ...The inverter will decelerate to 0Hz using ramp 33 RDEC1 reverse and accelerate to the frequency input with ramp 32 RACC1 The inverter will decelerate to standstill with ramp 33 RDEC1 Fig 7 Manual ope...

Page 16: ...10 kW or external voltage source 0V STOP output inhibited 0 1 V FMIN 10 V FMAX 2 10 V external power supply 0 20 mA 4 20 mA zero live signal Analog binary output SOUTA X1 10 Input signal Jumper J3 J4...

Page 17: ...X 16 PW Active power 0 18000 W X X X 17 VZK DC link voltage 0 350 900 V X X X 18 TIME Operating time from reset 0 0 960 0 h X X X 19 TOP Operating hours 0 60000 h X 66 SIN Not for use X 68 FIN X 83 S...

Page 18: ...cy 0 00 999 00 X X 29 FMAX2 Maximum frequency 4 00 50 00 999 00 Ramp generators X X 31 KSEL Characteristic set selector 0 1 2 3 0 always data set 1 1 data set 2 if 12 F 26 FF6 2 data set 2 if S2IND 1...

Page 19: ...MC0508 0 90 3 20 A Control functions X X 61 SOUTA Analog output X1 10 0 1 7 Sec 3 4 4 3 X X 62 S1OUT Digital output 1 X1 8 0 1 10 Sec 3 4 X X 63 S2OUT Digital output 2 X1 9 1 7 10 Sec 3 4 X X 64 SINA...

Page 20: ...RDEC1 or 35 RDEC2 reverses and accelerates with ramp 32 RACC1 or 34 RACC2 STR and STL 1 Important not fail safe Deceleration with deceleration ramp Drive decelerates with ramp 33 RDEC1 or 35 RDEC2 STR...

Page 21: ...r overtemperature Motor overloaded check drive or check PTC thermistor connection or jumper X5 PTC IIIIIIII IIIIIIII 8 times Inverter overtemperature Inverter overloaded check installation and ambient...

Page 22: ...patible ERR96 Connection to PAC 01 interrupted ERR97 PAC 01 invalid CS test Inverter faults E CPU Fault in processor pcb AUTOSTART in 72 START causes reset 1 E OFF Undervoltage no entry in fault memor...

Page 23: ...eration BRC 03 with integrated braking resistor Interference emission with EMC compliant installation mains input filter screened motor cable to class B limit to EN 55011 EN 55014 complies with EN 500...

Page 24: ...Imax 50 mA Important not short circuit proof not external voltage proof Reference potential ground X1 7 or X1 11 Programmable collective fault output voltage CW CCW motor standstill setpoint reached...

Page 25: ...ns 40 x170 mm hole size 4 8 mm For use with MOVITRAC type 0504 231 1 0508 231 1 cdf cyclic duration factor 6 3 NF 231 input filter Input filter type NF 005 231 NF 008 231 Part number 825 881 3 825 882...

Reviews: