Operating modes and limit values
Inverter operation
Operating Instructions – EDR..71 – 315, EDRN63 – 315
95
6.3
Inverter operation
6.3.1
Permitted voltage stress in inverter operation
Operating motors from
SEW‑EURODRIVE
on inverters is permitted if the pulse
voltages at the motor terminals indicated in the following figure are not exceeded:
0
200
400
600
800
1000
1200
1400
1600
1800
2000
[A]
[B]
0
0,2
0,4
0,6
0,8
1,0
1,2
1,4
[1]
27021600771392779
[A]
Permitted pulse U
LL
in V
[B]
Rise time in µs
[1]
Permitted pulse voltage for EDR../EDRN.. motors
INFORMATION
The permitted maximum PE voltage of 1200 V must not be exceeded in IT system
operation even in the event of an error.
INFORMATION
If the permitted pulse voltage is exceeded, you have to provide for according meas-
ures to limit it. Consult the manufacturer of the inverter.
INFORMATION
The maximum permitted nominal motor voltage for inverter operation is 500 V.
25896334/EN – 06/2019