Section 2
Installation Instructions
Part Number 020003999 6/14
2-7
Electrical
GENERAL
MINIMUM CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select the
wire size of the electrical supply. (Minimum circuit
ampacity is not the beverage/ice machine’s running amp
load.) The wire size (or gauge) is also dependent upon
location, materials used, length of run, etc., so it must be
determined by a qualified electrician.
ELECTRICAL REQUIREMENTS
Refer to Ice Machine Model/Serial Plate for voltage/
amperage specifications.
VOLTAGE
The standard voltage for MDH Series dispensers is
120VAC - 60Hz. A power cord is provided with 120VAC -
60Hz models only. MDH Series dispensers use a 1/7 hp
gearmotor.
MINIMUM CIRCUIT AMPERAGE CHART
* Does not include carbonator motor.
Grounding Instructions
This appliance must be grounded. In the event of
malfunction or breakdown, grounding provides a path of
least resistance for electric current to reduce the risk of
electric shock. This appliance is equipped with a cord
having an equipment-grounding conductor and a
grounding plug. The plug must be plugged into an
appropriate outlet that is properly installed and grounded
in accordance with all local codes and ordinances.
!
Warning
All wiring must conform to local, state and national
codes.
Important
Due to continuous improvements, this information is
for reference only. Please refer to the dispenser
serial number tag to verify electrical data. Serial tag
information overrides information listed on this
page.
MDH-302/402
Dispensers
Voltage/Cycle
Minimum
Circuit Amps
With Standard or 24"
Extended Merchandiser
(Non-crusher)
120/60
4.5 *
34" Extended
Merchandiser
(Non-crusher)
120/60
5.0 *
With Standard or 24"
Extended Merchandiser
(with Crusher)
120/60
5.25 *
34" Extended
Merchandiser
(with Crusher)
120/60
5.75 *
!
Warning
Risk of electrical shock. Connect to a properly
grounded outlet only.
!
Warning
Improper connection of the equipment-
grounding conductor can result in a risk of
electric shock. The conductor with insulation
having an outer surface that is green with or
without yellow stripes is the equipment
grounding conductor. If repair or replacement of
the cord or plug is necessary, do not connect
the equipment-grounding conductor to a live
terminal. Check with a qualified electrician or
serviceman if the grounding instructions are not
completely understood, or if in doubt as to
whether the appliance is properly grounded. Do
not modify the plug provided with the appliance
— if it will not fit the outlet, have a proper outlet
installed by a qualified electrician.