SENKO fireplaces
–
Instruction manual
36
7.4.
OLD FIREPLACE DISPOSAL
Once the fireplace is no longer fit for use it must be delivered to an
authorized disposal service specialized in recycling this type of waste.
It is
forbidden to dispose of the old fireplaces in the natural environment !
7.5.
SPARE PARTS
Only original spare parts by the manufacturer are to be used
. Should
non-original spare parts be used or should the repair be executed by an
unauthorized individual, the warranty will be void.
8. MALFUNCTIONS / CAUSES / SOLUTIONS
PROBLEM
POSSIBLE CAUSE
SOLUTION
Excessive combustion
– inability of primary
air regulation
uncontrolled primary
air inlet into firebox
– too
low chimney draught
(below 10 Pa)
completely seal fireplace base with
the floor on which the fireplace is
mounted (before lining work !)
– see
(14) Figure 13
completely close the ash box
reduce or close the primary air
automatic regulator
adjust the chimney flue draught in
accordance with chapter 4.2
.
check the joint of fireplace and
chimney and the chimney itself
check Chapters
4.2.
and
4.3.
Firebox door glass is
black and/or the firebox
is smoky (black soot)
faulty regulation
too much fuel in the
firebox
fuel too moist
inadequate fuel
excessive firebox
temperature
study chapters 5.1 and 5.2.3.
reduce the fuel quantity
use fuel with less than 17% of
relative moisture
use fuel as described in chapter 1.1.
reduce the fuel quantity and primary
air volume and adjust chimney flue
draught in accordance with chapter 5.1
There is noise from the
boiler
insufficient water
level in the central
heating system
insufficient water
pressure in the central
heating system
improper central
heating installation
refill the central heating system with
the necessary amount of water to
achieve 2.5 bar pressure
increase water pressure to 2,5 bar
execute the central heating
installation in accordance with
professional standards and DIN 4751
norm - part 1 for open systems, i.e.