SEQUENCER WITH
DIFFERENTIAL PRESSURE
SWITCH
Technical brochure
FI 72.0483.0720E
Page 20 sur 43
- 20 -Page 20 sur 43
- 20 - - 20 -
- 20 -
- 20 -
3: Display of the status of the dP order.
Gray: if the dP order is not present (if the measure is below the Min threshold).
Green: if the dP order is present (if the measure is above the Maxi threshold).
Notes: the dP order is temporized 1 second.
the dP order is always present if the Min and Max thresholds are set to 0.
4: Display of the low alarm dP status.
Gray: if the measure is above the low alarm threshold.
Red: if the measure is below the low alarm threshold.
Notes: the low alarm is temporized 5 seconds.
the low alarm is not generated if it is set to 0.
5: Display of the status of the 4 AON inputs I1, I2, I3 and I4
Gray: if the input is not present (= 0).
Green: if the input is present (= 1)
6: Information about state of declogging cycle.
Display of running time and countdown.
Display of last SV activated and the following SV.
If press on this area : link to the page « sequencer informations ».
7: Display of current protection level.
8: Display of the measure of the compressed air in Bar.
If the low alarm is present, the background of this area flashes red.
If press on this area: link to the page "Compressed air A/C".
Note: This area is not displayed if the device does not have this feature.
9: Display of status of the operating compressed air threshold.
Gray: if the measure is below the operating threshold.
Green: if the measure is above the operating threshold.
Notes: the operating threshold is temporized 1 second.
the operating threshold is always validated if the threshold is set to 0.
10: Display of the low compressed air alarm status.
Gray: if the measure is above the low alarm threshold.
Red: if the measure is below the low alarm threshold.
Notes: the low alarm is temporized 5 seconds.
the low alarm is not generated if it is set to 0.
11: Display of the CDM rejection in % (average over x minutes: see CDM manual).
If the alert or alarm is present (see CDM manual), the background of this area flashes red.
If press on this area: link to the
page “Rejection CDM”.
Note: This area is not displayed if the device does not have this feature.
12: Display of the status of the CDM rejection alarm (see CDM manual).
Gray: the CDM alarm is not present.
Red: the CDM alarm is present.
13: Display of the status of the CDM rejection alert (see CDM manual).
Gray: the CDM alert is not present.
Orange: the CDM alert is present.
14: If press on this area: link to the page « main menu ».