SEQUENCER WITH 

DIFFERENTIAL PRESSURE 

SWITCH

 

 

 

Technical brochure               

  FI 72.0483.0720E 

 

   Page 12 sur 43 

- 12 -Page 12 sur 43 

- 12 -  - 12 - 

- 12 - 

- 12 - 

 

VOLTAGE CHOICE : 

 
It is possible according to the version of the device to set differently the supply voltage and the solenoid valves 
voltage of that made by default in factory answering the ordered version. Warning: the device must be switched off. 
 
Notes: 

The supply choices "115V / 230V" or "24 / 48V" can be made only with order. 

If supply voltage "115V / 230V", the voltage choice of solenoid valves " 24V or 48V " can be made only with 
order 

 
See the table below for the possible settings according to the version of the box : 
 

ACCORDING THE VERSION 

SUPPLY VOLTAGE / 

SOLENOIDE VALVES 

VOLTAGE 

POSITION OF THE JUMPERS : 

230VAC / 230VAC 

48VAC / 48VAC 

 
 

                                
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

115VAC / 115VAC 

24VAC / 24VAC 

 

                                
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Jumper on : 
S1 / S2 / S4 
 
 
Nothing on : 
S3 / S5 / S6 

Jumper on : 
S1 / S2 / S3 
 
 
Nothing on : 
S4 / S5 / S6 

Summary of Contents for SET100DP

Page 1: ...Technical brochure FI 72 0483 0720E Page 1 sur 43 Outputs SV AC version Not ATEX version ATEX version ABS Box PC Box PLACE GUTENBERG 59175 TEMPLEMARS France Tel 33 0 3 20 60 49 49 Fax 33 0 3 20 95 59...

Page 2: ...RTU fieldbus Possibility of external gateway to other bus for example PROFIBUS DP The device is adjustable according to the use of it with several levels protected by passwords All the running paramet...

Page 3: ...1A to be protected by user Ambient operating temperature not ATEX version 20 60 C ATEX version 20 C 55 C Storage temperature 20 to 70 C Box ABS material IP65 not ATEX version PC material IP65 ATEX or...

Page 4: ...1 5 on sensor maxi scale 10 Bar from 0 to 50 C this accuracy takes into consideration linearity hysteresis temperature and repetitivity effects humidity 0 to 95 RH not condensed response time operati...

Page 5: ...Compressed air pressure connection Connection for 4 6mm tube A C 4 ISO16 4 20mA output dP 5 ISO16 4 20mA output A C 6 ISO16b AON input I1 7 ISO20b relay outputs 8 ISO16b AON input I2 9 ISO16b AON inp...

Page 6: ...nsion Box undersize of the box Individual cables version 1 common ground per SV 18xISO16 Multiconductors cables version 3 common 3 ground for 3x6 EV 3xISO20b Multiconductors cables version if version...

Page 7: ...al brochure FI 72 0483 0720E Page 7 sur 43 SV extension box 1 ISO20 supply 2 ISO16b extension com input 3 ISO16b extension com output Main box or SV extension box behind side of the box On the undersi...

Page 8: ...connection area see next page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 supply 2 extension com 3 CDM com 4 customer com 5 dP pressure connection clean air side Connection for 6 8mm tube 6 dP pressure connec...

Page 9: ...common ground per SV 18xISO16 Multiconductors cables version 3 common 3 ground for 3x6 EV 3xISO20b Clamping capacity of the cable glands Identify the cable glands used by the markings on the cable gla...

Page 10: ...AL PRESSURE SWITCH Technical brochure FI 72 0483 0720E Page 10 sur 43 SV extension box front side right side and left side note undersize of the box same as main box 1 supply 2 extension com input 3 e...

Page 11: ...fuse F3 caliber F1A F1A If version Pmax SV 45VA Supply voltage 230VAC 115VAC Solenoides valves voltage 230VAC 48VAC 24VAC 115VAC 48VAC 24VAC fuse F1 caliber F1A F1A fuse F2 caliber F1A F1A fuse F3 ca...

Page 12: ...the device must be switched off Notes The supply choices 115V 230V or 24 48V can be made only with order If supply voltage 115V 230V the voltage choice of solenoid valves 24V or 48V can be made only w...

Page 13: ...3 sur 43 230VAC 24VAC 230VAC 48VAC 115VAC 24VAC 115VAC 48VAC WARNING a modification of the supply voltage and or the solenoid valves voltage requires to update the descriptive label placed outside of...

Page 14: ...ection between 0 5 and 1 5 mm2 Power supply of the device The power supply for the device is connected in the upper part to the left of the board Communication extension CDM customer These connections...

Page 15: ...for recorder indicator etc max load 500 ohms Relay output K4 Run order report AON input I4 Forced running Relay output K3 High alarm dP AON input I1 Run order AON input I2 Compressed air control A C R...

Page 16: ...ed at the bottom and center of the board If version up to 18 SV by individual cable 1 common ground per SV If version up to 18 SV by multiconductors cable 1 common ground for 6 SV Connection of the ou...

Page 17: ...rsion with possibility of connection of two SV per output if version pmax SV 40VA 6 common 6 ground for 6x6 SV 6x common SV 6x ground SV Connection of the outputs solenoid valves 1 to 18 Each connecti...

Page 18: ...e rotary switch encoder in front of the associated number 1 to 8 Notes the connection of the power supply of the extension boxes is the same that the main box the connection of the SV outputs of the e...

Page 19: ...xcept when displaying the load loss dP Compressed air A C or rejection CDM pages Main page if no fault Main page if fault 1 Display of the measure of the load loss dP in daPa If a high or low dP alarm...

Page 20: ...f this area flashes red If press on this area link to the page Compressed air A C Note This area is not displayed if the device does not have this feature 9 Display of status of the operating compress...

Page 21: ...rage measured over this time see note 1 3 Display of measured values of the minimum and maximum pressure load loss dP observed Notes the minimum value is observed two minutes after the detection of th...

Page 22: ...30 operating points of the device 1 new point is added according to the value of the set step When the power is turned off the graphic is reset 2 Setting the graph advance 1 to 255 seconds Each time t...

Page 23: ...e graph advance 1 to 255 seconds Each time this timer expires a new point is added to the graph The value of the added point is the average measured over this time see note 1 3 Display of the instanta...

Page 24: ...5 counter of cycles done manufacturer 6 If press on this area return to main page 7 Displays the current protection level 8 reachable only at level 1 If press on this area the counter number of user c...

Page 25: ...o parameters menu page 5 if press on this area jump to system info page 6 if press on this area jump to manual running page 7 displays the current protection level Language page 1 if press on this are...

Page 26: ...he possibility to reset some counters for instance 1 If press on this area request to enter the password Depending on the password entered the corresponding level is activated Note If the password ent...

Page 27: ...rs of the compressed air A C control 4 if press on this area access to the parameters related to the fan function 5 if press on this area access to the parameters of the rejection control CDM 6 if pre...

Page 28: ...hours which is adjusted the ongoing cycle is stopped if stop in cycle and a declogging cycle is launched Note the presence of compressed air is necessary for this operation Remark T4 time is reset at...

Page 29: ...always in normal running Note An accelerated running request can also be given with the AON I3 input 5 Threshold High Alarm dP reachable at level 1 or above If measure dP is above this threshold more...

Page 30: ...The output is at 4mA if the load loss dP measure 0 daPa The output is at 20mA if the load loss dP measure indicated value Between 4 and 20 mA the output is linear and proportional to the load loss dP...

Page 31: ...e control is done with compressed air measure A C A C input the control is done with the state of the AON input A C I2 2 Choice of the control or not of the presence of compressed air out of decloggin...

Page 32: ...n of the fault in the main page INFLAT A C Svx where x is the number of the faulty SV This fault is auto reset when the control returns to OK 6 Operating threshold adjustable from 0 0 to 6 0 Bar reach...

Page 33: ...at 4mA if the compressed air A C measure 0 daPa The output is at 20mA if the compressed air A C measure indicated value Between 4 and 20 mA the output is linear and proportional to the compressed air...

Page 34: ...e stop of the fan is detected if I1 0 Note the running of the fan is detected if input I1 1 by dP loss the stop of the fan is detected if the load loss dP measure is lower than the value indicated on...

Page 35: ...and above n2 x PR ALARM see CDM instructions 3 Setting the x parameter of the rejection controller CDM from 1 to 33 reachable at level 1 and above x average duration see CDM instructions 4 Launching...

Page 36: ...ment of the number of SV used in the main box from 0 to 18 reachable at level 1 and above 3 to 10 Adjustment of the number of SV used in extension boxes 1 to 8 from 0 to 18 reachable at level 1 and ab...

Page 37: ...247 reachable at level 1 and above 2 Speed setting reachable at level 1 and above 2400 4800 9600 19200 38400 57600 or 115200 3 Type setting reachable at level 1 and above 8N1 8 bits no parity 1 stop 8...

Page 38: ...rmed independently of the input I1 the load loss dP pressure measure the input I2 the compressed air measure A C The value is downcounted as the cycles are done 2 Setting an SV number to activate it m...

Page 39: ...ompressed air is lost the cycle stops at the end of the idle time The cycle will resume when the compressed air reappears at the solenoid valve where it was stopped If detection of fan stop by input I...

Page 40: ...fault ELECTRIC FLT Svx if electrical fault on SV with x SV number If it is an installation with extension boxes short circuit electrical faults are identified by ELEC FLT SC Main If short circuit elec...

Page 41: ...if there is no fault or alarm contact between the terminals identified OUT1 and NO1 The relay is not energized if there is a fault an alarm or if the device is switched off contact between the termina...

Page 42: ...maxi pressure value of the range Adjustments made when device stabilised and at 20 C It is possible to adjust the zero pressure see load loss dP parameters WARRANTY The warranty does not apply in the...

Page 43: ...l regimes TT TN or IT Nevertheless we recommend that the device is supplied through the intermediary of an insulation transformer for which the primary is supplied between phases and not between phase...

Reviews: