ENFORCER Fingerprint Reader and Keypad
SECO-LARM U.S.A., Inc.
25
The fingerprint reader/keypad must be connected to a Request-to-Exit (RTE) button to be reset to
factory default settings. When resetting to factory default, user information is retained.
To reset the fingerprint reader/keypad to factory default settings, follow the steps below:
1.
Power off the fingerprint reader/keypad
2.
Hold down the egress button and power the fingerprint reader/keypad on, continuing to hold
down the egress button for at least 30 seconds after you hear 2 beeps and the LED turns
orange.
3.
After releasing the egress button, the LED will turn red indicating that the reset was successful.
Resetting the Fingerprint Reader/Keypad to Factory Default:
Setting Up an Interlock System with Two Keypads (Continued):
Programming the Interlock System:
When programming the interlock system, use the following general formula from within base
programming mode (see "Enter and Exit Base Programming Mode," pg. 9):
– Program the Interlock System function code (LED will change to steady orange)
– Disable or Enable the Interlock System
Disable or Enable the Interlock:
•
– Disable the interlock (factory default)
•
– Enable the interlock
NOTES:
•
The
key returns you to base programming mode (the LED will flash red). To program other
functions, press the function code for that function (LED becomes steady orange).
•
Exit programming mode by pressing the
key after all programming is completed. One beep
will sound and the LED will return to steady red. After 25 seconds of inactivity, the keypad will
automatically exit programming mode and return to standby.