6 Parameters List SV600 Series User Manual
72
Group A2: Motor 2 Parameters
Function
code
Name
Setting range
Default
Property
A2-44
Vector control slip gain
50 to 200 percent
100%
☆
A2-45
Time constant of speed loop filter
0.000 s ~ 0.100 s
0.000 s
☆
A2-46
Vector control over-excitation gain
0 ~ 200
64
☆
A2-47
Motoring torque upper limit source
in speed control
0: Set by A2-48
1: AI1
2: AI2
3.Potentiometer on keyboard
4: Pulse setting
5: Communication setting
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
100% in options 1-7 corresponds to A2-48
0
☆
A2-48
Digital setting of motoring torque
upper limit in speed control
0.0% ~ 200.0%
100% corresponds to motor rated current
150.0%
☆
A2-51
Excitation adjustment proportional
gain
0 ~ 20000
2000
☆
A2-52
Excitation adjustment integral gain
0 ~ 20000
1300
☆
A2-53
Torque adjustment proportional
gain
0 ~ 20000
2000
☆
A2-54
Torque adjustment integral gain
0 ~ 20000
1300
☆
A2-55
Speed loop integral property
Units digit: Integral separation
0: Invalid
1: Valid
0
☆
A2-59-60
Reserved
A2-61
Motor 2 control mode
0: Speed sensorless vector control (SVC)
1: Reserved
2: V/F control
0
★
A2-62
Acc./Dec. Time selection of Motor
2
0: Same as Motor 1
1: Acc./Dec. Time 1
2: Acc./Dec. Time 2
3: Acc./Dec. Time 3
4: Acc./Dec. Time 4
0
☆
A2-63
Motor 2 torque boost
0.0%: Automatic torque boost
0.1%~ 30.0%
Depends on
model
☆
A2-65
Motor 2 oscillation suppression
gain
0 ~ 100
Depends on
model
☆