6 Parameters List SV600 Series User Manual
60
Group P8:Auxiliary Functions
Function
code
Name
Setting range
Default
Property
P8-51
Sleep frequency
0.00 Hz ~ 50.00 Hz
0.00 Hz
☆
P8-52
Sleep delay time
0.0 s ~ 6500.0s
0.0 s
☆
P8-53
Current running time reached
setting
0.0~6500.0min
0.0 Min
☆
P8-54
Output
power
correction
coefficient
0.00% ~ 200.0%
100.0%
☆
Group P9: Fault and Protection
Function
code
Name
Setting range
Default
Property
P9-00
Motor overload protection
selection
0: Invalid
1: Valid
1
☆
P9-01
Motor overload protection
gain
0.20-10.00
1.00
☆
P9-02
Motor
overload
warning
coefficient
50%-100%
80%
☆
P9-03
Overvoltage stall gain
0 ~ 100
100
☆
P9-04
Overvoltage stall protection
voltage
120%~150%
120%
☆
P9-05
Overcurrent stall gain
0 ~ 100
20
☆
P9-06
Overcurrent stall protection
current
100~200%
150%
☆
P9-07
Protection for short circuit to
ground when power on
0: Invalid
1: Valid
1
☆
P9-08
Braking voltage of the built-in
braking unit
200.0~2000.0V
Depends
on model
★
P9-09
Fault automatic reset times
0 ~ 20
0
☆
P9-10
DO action selection during
fault automatic reset
0: No action
1: Action
0
☆
P9-11
Fault auto reset interval time
0.1 s ~ 100.0 s
1.0 s
☆
P9-12
Input loss phase protection
and contactor pull-in selection
Units digit: Input loss phase protection
0: Invalid
1: Valid
Tens digit: Contactor pull-in protection
0: Invalid
1: Valid
1
☆
P9-13
Output loss phase protection
0: Invalid
1: Valid
1
☆
P9-14
Fault 1 type
0: No fault
1: Reserved
2: Overcurrent during acceleration
3: Overcurrent during decelerationt
4: Overcurrent at constant speed
5: Overvoltage during acceleration
6: Overvoltage during deceleration
7: Overvoltage at constant speed
-
●
P9-15
Fault 2 type
-
●
P9-16
Fault 3 type
●