SV600 Series User Manual 7 Parameter Description
97
Table 7-2 Acc./Dec. Time Selection
Terminal 2
Terminal 1
Acc./ Dec. Time Selection
Corresponding parameters
OFF
OFF
Acc./Dec. Time 1
P0-17, P0-18
OFF
ON
Acc./Dec. Time 2
P8-03, P8-04
ON
OFF
Acc./Dec. Time 3
P8-05, P8-06
ON
ON
Acc./Dec. Time 4
P8-07, P8-08
18: Frequency source switchover
The terminal is used to perform switchover between two frequency sources according to the
setting in P0-07.
19: UP/DOWN settings clear (Terminal, Keyboard)
The terminal is used to clear the modification by the DI with UP/DOWN function or the UP and
DOWN arrow on the keyboard, returning the set frequency to the value of P0-08.
20: Control command switchover terminal 1
The terminal is used to perform switchover between terminal control and keyboard control or
switchover between communication control and keyboard control.
When it’s valid, the control mode becomes keyboard control.
21: Acceleration/Deceleration prohibit
The inverter will maintain the current frequency running except for STOP command valid.
22: PID pause
When the DI is valid, the inverter will stop the PID function and maintain the current frequency
running.
23: PLC status reset
24: Swing Pause
The inverter outputs the central frequency, and the swing frequency function pauses.
25: Count input
26: Count reset
27: Length count input
28: Length reset
29: Torque control prohibit
The inverter is prohibited from torque control and enters the speed control mode.
30: HDI (Pulse) frequency input
31: Reserved
32: Immediate DC braking
33: External Fault Input (NC Normal Close)
When the DI is valid, the inverter reports Err15 and stops.
34: Frequency modification enable
After the DI is valid, the inverter does not respond to any frequency modification.
35: Reverse direction of PID action
After the DI is valid, the PID action direction is reversed to the direction set in PA-03.
36: External Stop terminal 1
37: Control command switchover terminal 2
It is used to perform switchover between terminal control and communication control. If the DI