SV600 Series User Manual 7 Parameter Description
143
Pb-01
Swing frequuency amplitude
0.0% ~ 100.0%
0.0%
☆
Pb-02
Jump frequency amplitude
0.0% ~ 50.0%
0.0%
☆
This parameter is used to determine the swing amplitude and jump frequency amplitude.
The swing frequency is limited by the frequency upper limit and frequency lower limit.
When Pb-00 = 0, the actual swing amplitude AW =Set frequency (Fset)*Pb-01.
When Pb-00 = 0, the actual swing amplitude AW =P0-10*Pb-01.
Jump frequency = Swing amplitude AW * Pb-02
Function
code
Name
Setting range
Default
Property
Pb-03
Swing cycle period
0.1 s ~ 3000.0 s
10.0 s
☆
Pb-04
Triangular wave rising time coefficient
0.1% ~ 100.0%
50.0%
☆
Pb-03 specifies the time of a complete swing frequency cycle.
Pb-04 specifies the triangular wave rising time (percentage of Pb-03).
Triangular wave rising time = Pb-03*Pb-04 (unit: s)
Triangular wave falling time = Pb-03- Pb-03*Pb-04(unit: s)
Function
code
Name
Setting range
Default
Property
Pb-05
Set length
0m ~ 65535m
1000m
☆
Pb-06
Actual length
0m ~ 65535m
0m
☆
Pb-07
Number of pulses per meter
0.1-6553.5
100.0
☆
The preceding parameters are used for fixed length control.
The length information is collected by DI terminals. Pb-06 (Actual length) is calculated by
dividing the number of pulses collected by the DI terminal by Pb-07 (Number of pulses per
meter).
When the actual length Pb-06 exceeds the set length in Pb-05, the DO terminal allocated with
function 10 (Length reached) becomes ON.
During the fixed length control, the length reset operation can be performed via the DI terminal
allocated with function 28. For details, see the descriptions of P4-00 to P4-09.
Allocate corresponding DI terminal with function 27 (Length count input) in applications. If the
pulse frequency is high, HDI must be used.
Function
code
Name
Setting range
Default
Property
Pb-08
Set count value
1-65535
1000
☆
Pb-09
Count value
1-65535
1000
☆
The count value needs to be collected by DI terminal. Allocate the corresponding DI terminal with
function 25 (Counter input) in applications. If the pulse frequency is high, HDI must be used.
When the count value reaches the set count value (Pb-08), the DO terminal allocated with
function 8 (Set count value reached) becomes ON. Then the counter stops counting.