SV600 Series User Manual 7 Parameter Description
133
time reached (Err26)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
P9-49
Fault protection action
selection 3
Units digit: User-defined fault 1 (Err27)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
Tens digit: User-defined fault 2 (Err28)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
Hundreds digit: Accumulative power-on time
reached (Err29)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
Thousands digit:Underload(Err30)
0: Freely stop
1: Stop according to the stop mode
2: Run at 7% of motor rated frequency and
run at the set frequency when the load
recovers
Ten thousands: PID feedback loss during
running (Err31)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
00000
☆
P9-50
Fault protection action
selection 4
Units digit: Speed deviation too large (Err42)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
Tens digit: Motor overspeed (Err43)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
Hundreds digit: Initial position error (Err51)
0: Freely stop
1: Stop according to the stop mode
2: Continue running
00000
☆
0: Freely stop
When fault occurs, the inverter displays Err** and directly stops.
1: Stop according to the stop mode