SV600 Series User Manual 7 Parameter Description
149
code
Pd-03
MODBUS response delay
0 ~ 20ms
2
☆
The response delay is the interval between the end of the inverter data reception and the sending
of data to the upper device.
Function
code
Name
Setting range
Default
Property
Pd-04
Serial communication timeout
0.0s: Invalid
0.1 ~ 60.0 s
0.0
☆
When serial communication fails and exceeds the time set in Pd-04, the inverter will report
communication error. When Pd-04=0.0, the protection function is invalid.
Function
code
Name
Setting range
Default
Property
Pd-05
MODBUS
0: Non-standard MODBUS protocol
1: Standard MODBUS protocol
1
☆
When Pd-05=1, standard MODBUS protocol is selected.
When Pd-05=0, the slave device will reply one more byte than standard MODBUS protocol when
replying the reading command from the upper device.
Function
code
Name
Setting range
Default
Property
Pd-06
Communication reading current resolution
0: 0.01 A
1: 0.1 A
0
☆