7 Parameter Description SV600 Series User Manual
158
Function
code
Name
Setting range
Default
Property
A2-40
Switching frequency 1
0.00-A2-43
5.00 Hz
☆
A2-41
Speed
loop
proportional gain2
1-100
20
☆
A2-42
Speed loop integration
time2
0.01 s ~ 10.00 s
1.00 s
☆
A2-43
Switching frequency 2
A2-40 ~ maximum frequency
10.00 Hz
☆
A2-44
Vector control slip
gain
50 to 200 percent
100%
☆
A2-45
Time
constant
of
speed loop filter
0.000 s ~ 0.100 s
0.000 s
☆
A2-46
Vector
control
over-excitation gain
0 ~ 200
64
☆
A2-47
Motoring
torque
upper limit source in
speed control
0: Set by A2-48
1: AI1
2: AI2
3.Potentiometer on keyboard
4: Pulse setting
5: Communication setting
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
100% in options 1-7 corresponds to A2-48
0
☆
A2-48
Digital
setting
of
motoring torque upper
limit in speed control
0.0% ~ 200.0%
100% corresponds to motor rated current
150.0%
☆
A2-51
Excitation adjustment
proportional gain
0 ~ 20000
2000
☆
A2-52
Excitation adjustment
integral gain
0 ~ 20000
1300
☆
A2-53
Torque
adjustment
proportional gain
0 ~ 20000
2000
☆
A2-54
Torque
adjustment
integral gain
0 ~ 20000
1300
☆
A2-55
Speed loop integral
property
Units digit: Integral separation
0: Invalid
1: Valid
0
☆
A2-59-60
Reserved
A2-61
Motor 2 control mode
0: Speed sensorless vector control (SVC)
1: Reserved
2: V/F control
0
★
A2-62
Acc./Dec.
Time
0: Same as Motor 1
0
☆