7 Parameter Description SV600 Series User Manual
152
Group A0: Torque Control Parameters
Function
code
Name
Setting range
Default
Property
A0-00
Speed/Torque control selection
0: Speed control
1: Torque control
0
★
It is used to select the inverter's control mode: speed control or torque control.
If the multi-function terminal DI with function 46 (Speed control/Torque control switchover) is
OFF, the control mode is determined by A0-00. If multi-function terminal DI with function 46 is
ON, the control mode is reverse to the value of A0-00.
However, if multi-function terminal DI with function 29 (Torque control prohibited) is ON, the
inverter is fixed to run in the speed control mode.
Function
code
Name
Setting range
Default
Property
A0-01
Torque setting source selection
0: Set by A0-03
1: AI1
2: AI2
3: Reserved
4: PULSE setting (HDI)
5: Communication setting
6: MIN (AI1, AI2)
7: MAX (AI1, AI2)
(100% of 1-7 options, corresponding
to the value set in A0-03)
0
★
A0-03
Torque digital setting
-200.0% ~ 200.0%
150.0%
☆
A0-01 is used to set the torque setting source.
The torque setting is a relative value. 100.0% corresponds to the inverter's rated torque.
The setting range of A0-03 is -200.0% to 200.0%, indicating the inverter's maximum torque is
twice of the inverter's rated torque.
If the torque setting is positive, the inverter rotates in forward direction. If the torque setting is
negative, the inverter rotates in reverse direction.
100% of 1~7 selection in A0-01, corresponding to the value set in A0-03.
Function
code
Name
Setting range
Default
Property
A0-05
Forward maximum frequency of
torque control
0.00 Hz ~ maximum frequency
50.00 Hz
☆
A0-06
Reverse maximum frequency of
torque control
0.00 Hz ~ maximum frequency
50.00 Hz
☆
A0-07
Torque control acceleration time
0.00 s ~ 65000 s
0.00 s
☆
A0-08
Torque control deceleration time
0.00 s ~ 65000 s
0.00 s
☆
A0-05 and A0-06 are used to set the maximum frequency in forward or reverse rotation in torque