7
Date Code 20050919
Instruction Manual
SEL-387-0, -5, -6 Relay
SEL-387 Relay Command Summary
SER
d1 d2
Show rows in the Sequential Events Recorder (SER) event report from date
d1
to
d2
.
Entry of dates is dependent on the Date Format setting DATE_F (= MDY or YMD).
SER
m n
Show rows
m
through
n
in the Sequential Events Recorder (SER) event report.
SER
n
Show the latest
n
rows in the Sequential Events Recorder (SER) event report.
SER C
Clear the Sequential Events Recorder (SER) event reports from memory.
SET
n
Change relay group settings (overcurrent, differential, etc.). For the
SET
commands, parameter
n
is the setting
name at which to begin editing settings. If parameter
n
is not entered, setting editing starts at the first setting.
SET G
Change global settings.
SET P
n
Change port settings.
SET R
Change Sequential Events Recorder (SER) settings.
SHO
n
Show relay group
n
settings. Shows active group if
n
is not specified.
SHO G
Show relay global settings.
SHO P
Show port settings and identification of port to which user is connected.
SHO P
n
Show port settings for port
n
(
n
=1, 2, 3, 4).
SHO R
Show Sequential Events Recorder (SER) settings.
STA
Show relay self-test status.
TAR
n k
Show Relay Word row
n
status (
n
= 0 through 41). Enter number
k
to scroll Relay Word row
n
status
k
times on
screen.
Append F to display targets on the front panel, second row of LEDs.
TAR R
Return front-panel LED targets to regular operation and reset the tripping front-panel targets.
All commands that begin TFE apply to the SEL-387-5 and SEL-387-6 Relays
TFE
Displays cumulative and individual through-fault event data. The twenty (20) most recent individual events are
displayed.
TFE
n
Displays cumulative and individual through-fault event data. The
n
most recent individual events are displayed,
where
n
= 1 to 1200.
TFE A
Displays cumulative and individual through-fault event data. All the most recent individual events are
displayed, up to 1200.
TFE C
Clears/resets cumulative and individual through-fault event data.
TFE P
Preloads cumulative through-fault event data.
TFE R
Clears/resets cumulative and individual through-fault event data.
All commands that begin THE apply to the SEL-387-6 Relay
THE
Displays a thermal monitor report that indicates the present thermal status of the transformer.
THE
n
Displays saved thermal monitor report
n
where
n
= 1 is the most recently saved report.
THE C
Clears the hourly profile, daily profile, and thermal event data archives.
THE D
x y
Retrives daily profile data from day
x
to day
y
. If
x
and
y
are omitted, retrieves entire profile data. If
x
or
y
is
omitted, retrieves profile from day
x
(
y
) to present.
THE H
x y
Retrives hourly profile data from day
x
to day
y
. If
x
and
y
are omitted, retrieves entire profile data. If
x
or
y
is
omitted, retries profile from day
x
(
y
) to present.
THE P
n
Loads preset value of accumulated insulation loss of life.
THE R
Clears the hourly profile, daily profile, and thermal event data archives and resets the total loss-of-life values.
THE T
Displays the four temperature inputs received from an SEL-2032, an SEL-2030, or
an SEL-2020 Communications Processor.
Access Level 2
Commands
The Access Level 2 commands primarily allow the user to change settings or operate relay
parameters and output contacts. All Access Level 1 commands can also be executed from Access
Level 2. The screen prompt is: =>>
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...