4.33
Date Code 20050919
Instruction Manual
SEL-387-0, -5, -6 Relay
Control Logic
Relay Word Bits
NDEM3
Winding 3 residual demand current threshold exceeded
OC3
Breaker 3
OPEN
command execution
13
50Q31
Winding 3 neg.-seq. definite-time O/C Level 1 element picked up
50Q31T
Winding 3 neg.-seq. definite-time O/C Level 1 element timed out
50Q32
Winding 3 neg.-seq. instantaneous O/C Level 2 element picked up
51Q3
Winding 3 neg.-seq. inverse-time O/C element picked up
51Q3T
Winding 3 neg.-seq. inverse-time O/C element timed out
51Q3R
Winding 3 neg.-seq. inverse-time O/C 51Q3 element is reset
QDEM3
Winding 3 neg.-seq. demand current threshold exceeded
CC3
Breaker 3
CLOSE
command execution
14
50P41
Winding 4 phase definite-time O/C Level 1 element picked up
50P41T
Winding 4 phase definite-time O/C Level 1 element timed out
50P42
Winding 4 phase instantaneous O/C Level 2 element picked up
51P4
Winding 4 phase inverse-time O/C element picked up
51P4T
Winding 4 phase inverse-time O/C element timed out
51P4R
Winding 4 phase inverse-time O/C 51P4 element is reset
PDEM4
Winding 4 phase demand current threshold exceeded
CTS
Current transformer saturation
15
50A43
Winding 4 A-phase instantaneous O/C Level 3 element picked up
50B43
Winding 4 B-phase instantaneous O/C Level 3 element picked up
50C43
Winding 4 C-phase instantaneous O/C Level 3 element picked up
50P43
50A43 + 50B43 + 50C43
50A44
Winding 4 A-phase instantaneous O/C Level 4 element picked up
50B44
Winding 4 B-phase instantaneous O/C Level 4 element picked up
50C44
Winding 4 C-phase instantaneous O/C Level 4 element picked up
50P44
50A44 + 50B44 + 50C44
16
50N41
Winding 4 residual definite-time O/C Level 1 element picked up
50N41T
Winding 4 residual definite-time O/C Level 1 element timed out
50N42
Winding 4 residual instantaneous O/C Level 2 element picked up
51N4
Winding 4 residual inverse-time O/C element picked up
51N4T
Winding 4 residual inverse-time O/C element timed out
51N4R
Winding 4 residual inverse-time O/C 51N4 element is reset
NDEM4
Winding 4 residual demand current threshold exceeded
OC4
Breaker 4
OPEN
command execution
17
50Q41
Winding 4 neg.-seq. definite-time O/C element picked up
50Q41T
Winding 4 neg.-seq. definite-time O/C element timed out
50Q42
Winding 4 neg.-seq. instantaneous O/C Level 2 element picked up
51Q4
Winding 4 neg.-seq. inverse-time O/C element picked up
51Q4T
Winding 4 neg.-seq. inverse-time O/C element timed out
51Q4R
Winding 4 neg.-seq. inverse-time O/C 51Q4 element is reset
Table 4.10
Relay Word Bit Definitions
(Sheet 4 of 13)
Row
Bit
Definition
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...