2
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20050919
SEL-387 Relay Command Summary
MET H
Generate harmonic spectrum report for all input currents, showing first to fifteenth harmonic levels in secondary
amperes.
MET P
k
Display peak demand metering data, in primary amperes. Enter number
k
to scroll metering
k
times on screen.
MET RD
n
Reset demand metering values (
n
= 1, 2, 3, 4, A).
MET RP
n
Reset peak demand metering values (
n
= 1, 2, 3, 4, A).
MET SEC
k
Display metering data (magnitude and phase angle), in secondary amperes. Enter number
k
to scroll metering
k
times on screen.
MET T
Report temperature values of up to 24 RTD inputs (SEL-387-5 and SEL-387-6 Relays only).
QUI
Quit. Returns to Access Level 0. Returns front-panel LEDs to the default targets.
SER
d1
Show rows in the Sequential Events Recorder (SER) event report for date
d1
.
SER
d1 d2
Show rows in the Sequential Events Recorder (SER) event report from date
d1
to
d2
. Entry of dates is dependent
on the Date Format setting DATE_F (= MDY or YMD).
SER
m n
Show rows
m
through
n
in the Sequential Events Recorder (SER) event report.
SER
n
Show the latest
n
rows in the Sequential Events Recorder (SER) event report.
SER C
Clear the Sequential Events Recorder (SER) event reports from memory.
SHO
n
Show relay group
n
settings. Shows active group if
n
is not specified.
SHO G
Show relay global settings.
SHO P
Show port settings and identification of port to which user is connected.
SHO P
n
Show port settings for port
n
(
n
=1, 2, 3, 4).
SHO R
Show Sequential Events Recorder (SER) settings.
STA
Show relay self-test status.
STA C
Clear relay status report from memory and reboot the relay.
TAR
n k
Show Relay Word row
n
status (
n
= 0 through 41). Enter number
k
to scroll Relay Word row
n
status
k
times on
screen.
Append
F
to display targets on the front panel, second row of LEDs.
TAR R
Return front-panel LED targets to regular operation and reset the tripping front-panel targets.
All commands that begin TFE apply to the SEL-387-5 and SEL-387-6 Relays
TFE
Displays cumulative and individual through-fault event data. The twenty (20) most recent individual events are
displayed.
TFE
n
Displays cumulative and individual through-fault event data. The
n
most recent individual events are displayed,
where
n
= 1 to 1200.
TFE A
Displays cumulative and individual through-fault event data. All the most recent individual events are displayed,
up to 1200.
TFE C
Clears/resets cumulative and individual through-fault event data.
TFE P
Preloads cumulative through-fault event data.
TFE R
Clears/resets cumulative and individual through-fault event data.
All commands that begin THE apply to the SEL-387-6 Relay
THE
Displays a thermal monitor report that indicates the present thermal status of the transformer.
THE
n
Displays saved thermal monitor report
n
where
n
= 1 is the most recently saved report.
THE C
Clears the hourly profile, daily profile, and thermal event data archives.
THE D
x y
Retrives daily profile data from day
x
to day
y
.
If
x
and
y
are omitted, retrieves entire profile data.
If
x
or
y
is omitted, retrieves profile from day
x
(
y
) to present.
Access Level 1
Commands
The Access Level 1 commands primarily allow the user to look at information
(e.g., settings, metering, etc.), but not to change it. The screen prompt is: =>
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...