24 of 38
SEL-387-0, -5, -6 Relay Settings Sheet Group Settings (SET Command) Example
Trip Logic
SEL-387-0, -5, -6 Relay
Instruction Manual
Date Code 20050919
Date _______________
Group______________
Trip Logic
TR1
=
51P1T +51Q1T + OC1 + LB3
TR2
=
51P2T + 51Q2T + OC2
TR3
=
50P31 + 51P3T + OC3
TR4
=
87R + 87U
TR5
=
0
ULTR1
=
!50P13
ULTR2
=
!50P23
ULTR3
=
!50P33
ULTR4
=
!(50P13 + 50P23 + 50P33)
ULTR5
=
0
Close Logic
52A1
=
IN101
52A2
=
IN102
52A3
=
IN103
52A4
=
0
CL1
=
CC1 + LB4 + /IN104
CL2
=
CC2 + /IN105
CL3
=
CC3 + /IN106
CL4
=
0
ULCL1
=
TRIP1 + TRIP4
ULCL2
=
TRIP2 + TRIP4
ULCL3
=
TRIP3 + TRIP4
ULCL4
=
0
Event Report Triggering
ER
=
/50P11 + /51P1 +/51Q1 + /51P2 + /51Q2 + /51P3
Output Contact Logic (Standard Outputs)
OUT101
=
TRIP1
OUT102
=
TRIP2
OUT103
=
TRIP3
OUT104
=
TRIP4
OUT105
=
CLS1