6.13
Date Code 20050919
Instruction Manual
SEL-387-0, -5, -6 Relay
Setting the Relay
Default Settings
(Continued from previous page)
TR1 = 51P1T + 51Q1T + OC1 + LB3
TR2 =51P2T + 51Q2T + OC2
TR3 =50P31 + 51P3T + OC3
TR4 =87R + 87U
TR5 =0
ULTR1 =!50P13
ULTR2 =!50P23
Press RETURN to continue
ULTR3 =!50P33
ULTR4 =!(50P13 + 50P23 + 50P33)
ULTR5 =0
52A1 =IN101
52A2 =IN102
52A3 =IN103
52A4 =0
CL1 =CC1 + LB4 + /IN104
CL2 =CC2 + /IN105
CL3 =CC3 + /IN106
CL4 =0
ULCL1 =TRIP1 + TRIP4
ULCL2 =TRIP2 + TRIP4
ULCL3 =TRIP3 + TRIP4
ULCL4 =0
ER =/50P11 + /51P1 + /51Q1 + /51P2 + /51Q2 + /51P3
OUT101 =TRIP1
OUT102 =TRIP2
OUT103 =TRIP3
OUT104 =TRIP4
Press RETURN to continue
OUT105 =CLS1
OUT106 =CLS2
OUT107 =CLS3
SCEUSE 46.8
GR1CHK A526
=>>
The Group settings shown above are the only settings which are different from
the 5 A relay settings. The Global, Port, and SER settings remain the same.