5.19
Date Code 20050919
Instruction Manual
SEL-387-0, -5, -6 Relay
Metering and Monitoring
Thermal Monitor (SEL-387-6 Relay)
=>>
THE H <Enter>
XFMR 1 Date: 04/24/00 Time: 13:20:03.956
STATION A
FID=SEL-387-6-X117-V0-Z001001-D20000419
Transformer 1
Ambient Calc Measured Load
Date Time Temp Top Oil Top Oil Hot Spot Current FAA
04/24/00 13:00* 15.0 32.5 -0- 32.7 0.04 0.0
04/24/00 12:00* 15.0 32.5 -0- 32.8 0.05 0.0
Transformer 2
Ambient Calc Measured Load
Date Time Temp Top Oil Top Oil Hot Spot Current FAA
04/24/00 13:00* 15.0 32.5 -0- 32.5 0.01 0.0
04/24/00 12:00* 15.0 32.5 -0- 32.5 0.02 0.0
Transformer 3
Ambient Calc Measured Load
Date Time Temp Top Oil Top Oil Hot Spot Current FAA
04/24/00 13:00* 15.0 32.5 -0- 32.7 0.05 0.0
04/24/00 12:00* 15.0 32.5 -0- 32.7 0.06 0.0
=>>
Daily Profile Data Report Function (THE D Command)
The relay stores the following on a daily basis (at midnight) for the last 30
days:
➤
Maximum ambient temperature
➤
Maximum calculated top-oil temperature
➤
Maximum measured top-oil temperature
➤
Maximum winding hot-spot temperature
➤
Maximum per-unit load
➤
Maximum insulation aging acceleration factor (FAA)
➤
Daily 24-hour accumulated loss of life (value of accumulated
24-hour loss of life at midnight)
➤
Total accumulated loss of life (sum of the daily 24-hour
accumulated loss of life values)
➤
* showing a communication failure
The format for the
THE D
report is as follows:
=>
THE D <Enter>
XFMR 1 Date: 04/25/00 Time: 00:00:43.248
STATION A
FID=SEL-387-6-X117-V0-Z001001-D20000419
Transformer 1
Max Max Calc Max Msd Max
Date Ambient Top Oil Top Oil Hot Spot Max Load Max FAA RLOL TLOL
04/25/00 15.0 32.6 -0- 34.2 0.48 0.0 0.00 0.00
Transformer 2
Max Max Calc Max Msd Max
Date Ambient Top Oil Top Oil Hot Spot Max Load Max FAA RLOL TLOL
04/25/00 15.0 32.6 -0- 34.2 0.48 0.0 0.00 0.00
Transformer 3
Max Max Calc Max Msd Max
Date Ambient Top Oil Top Oil Hot Spot Max Load Max FAA RLOL TLOL
04/25/00 15.0 32.6 -0- 34.2 0.48 0.0 0.00 0.00
=>>
NOTE:
When the thermal model is
applied on one three-phase
transformer (XTYPE = 3), the
SEL-387-6 displays only the values for
Transformer 1; but when the thermal
model is applied on a set of three
single-phase transformers
(XTYPE = 1), the SEL-387-6 displays
the values for Transformer 1,
Transformer 2, and Transformer 3.
Summary of Contents for SEL-387-0
Page 10: ...This page intentionally left blank ...
Page 16: ...This page intentionally left blank ...
Page 56: ...This page intentionally left blank ...
Page 350: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 456: ...This page intentionally left blank ...
Page 494: ...This page intentionally left blank ...
Page 528: ...This page intentionally left blank ...