Hardware Manual PCD1.M2110R1 │ Document 27-619 │ Version ENG 04 │ 2018-08-20
Saia-Burgess Controls AG
Plug-In I/O Module for slot A
Inputs/Outputs (I/O)
4-13
4
4.2
Plug-In I/O Module for slot A
4.2.1
Analogue outputs
PCD7.W600 4 analogue outputs with 12 bits resolution
This analogue outputs module (0 to +10 V) can be plugged on the socket A of a
PCD1.M2_ / .M0_ instead of a communication interface.
The configuration of the outputs takes place in the Device Configurator like on-
board I/O’s
X3
IO0
IO1
X2
X1
X0
PCD7.W600
29 .. 20
X3
20
21
22
23
24
25
26
27
28
29
A0 +
A0 -
PGND
A1 +
A1 -
A2 +
A2 -
PGND
A3 +
A3 -
Terminal Block
X2
Earthing bar
General specifications
Technical data
Module compatibility
PCD1.M2xxx, PCD1.M0160E0, PCD1.M2110R1
Module current consumption
V+ 25 mA / +5 V 30 mA
Number of outputs
4
Terminals
1 plug-in screw terminal block, 10-pole, 3.5 mm for wiring
up to 1 mm
2
Isolation
No isolation between channels and/or PCD
Output signal range &
resolution
With D/A converter 12 bits
Nominal range: 0…+10 V
Resolution 2.6 mV of least significant bit (LSB)
Monotonicity
Yes
Output impedance (max.)
0.7 Ω
Allowable load resistance
≥3 kΩ
Allowable capacitive load
≤20 nF