SATEL INTEGRA
Plus
73
In case of the C
ONTACT
ID
(
SELECTED
) and SIA
(
SELECTED
)
formats, indicate the events
which are to be reported, entering for them any code different from "00" (a code
consistent with the format specification will be sent, not the entered one). The events
for which the "00" code has been programmed will not be reported.
9.1.7 Test transmissions
The test transmission may be sent:
at a specified time. The test transmission code will be sent regularly at a defined time. The
number of days between transmissions and the time of sending transmission are
programmed.
in specified time intervals. The test transmission code will be sent after expiry of a defined
time after the last transmission (irrespective of whether it was a test transmission or a code
of another event was sent). For each monitoring station, the number of days, hours and
minutes between transmission can be individually programmed.
9.2 Starting the reporting
9.2.1 Telephone reporting
1. Enable the R
EPORTING
–
TELEPHONE option.
2. Using the telephone options (see: section T
ELEPHONE OPTIONS
p. 56):
– determine how the telephone numbers should be dialed (T
ONE DIALING
option and – in
case of the pulse dialing – P
ULSE DIALING
1/1,5
(
OFF
:1/2)
option);
– determine whether the control panel, prior to dialing the number, should check the
telephone line for dialing signal (N
O DIAL TONE TEST
option).
3. Determine whether the event codes will be sent to both monitoring stations or to one of
them only (S
TATION
1
OR
2
/ S
TATION
1 / S
TATION
2 / S
TATION
1
AND
2).
4. Program the following for the monitoring station to which event codes are to be sent:
– telephone number,
– reporting format in which the codes will be sent,
– the number of attempts to connect to the station after which, if there is no connection,
the control panel will suspend reporting (R
EPETITIONS
),
– time for which reporting will be suspended after the programmed number of attempts to
establish connection with the station has been made (S
USPEND TIME
),
– identifiers with which the events will be sent,
– events assignment (if S
TATION
1
AND
2
is selected);
– advanced options (if Ademco Express, Contact ID, SIA or TELIM format is selected).
5. If a reporting format other than C
ONTACT
ID
(
FULL
) or SIA
(
FULL
) is selected:
– assign identifiers to the partitions, zones, keypads and expansion modules;
– program the codes for events which are to be reported.
6. Define the parameters of test transmissions.
9.2.2 Reporting via Ethernet network
The ETHM-1 module must be connected to the control panel.
Events in TELIM format cannot be sent through Ethernet network.
1. Enable the R
EPORTING
-
ETHM-1
option.
2. Determine whether the event codes will be sent to both monitoring stations or to one of
them only (S
TATION
1
OR
2
/ S
TATION
1 / S
TATION
2 / S
TATION
1
AND
2).