
SATEL INTEGRA
Plus
51
98. R
EMOTE SWITCH
– similarly as types 64-79, but the numbers of remote switches must be
selected.
99. A
CCESS CARD READ
– signals read-in of the user card.
100. C
ARD
H
OLD
–
DOWN
– signals holding the user card.
101. C
ARD READ
–
EXPANDER
– signals that the card has been read in indicated
modules/keypads.
The 101. C
ARD READ
–
EXPANDER
type output may be used for execution of the access
control function from INT-KLCDR keypad. To do so:
in the output settings, indicate the keypad on which reading in the card will activate
the output, and the partitions from which the users will be able to open the door;
in the keypad settings, assign the door opening function to presenting / holding the
card and indicate the 101. C
ARD READ
–
EXPANDER
type zone as the door to be
opened.
102. L
INK TROUBLE
–
WIRELESS ZONE
– signals lack of communication with wireless devices
assigned to the selected zones.
103. L
INK TROUBLE
–
WIRELESS OUTPUT
– signals lack of communication with wireless devices
assigned to the selected outputs.
104. W
IRELESS DEVICE
–
LOW BATTERY
– signals some problems with power supply of wireless
devices.
105. S
HUTTER UP
– dedicated for raising the roll shutters. It becomes active after violation of
selected zones or disarming of selected partitions. It can also be triggered from the
keypad, by means of the user function O
UTS CONTROL
. The cut-off time programmed for
the output should be longer than that required for raising the roll shutters.
106. S
HUTTER DOWN
– dedicated for lowering the roll shutters. It becomes active after
violation of selected zones or arming of selected partitions (upon starting the arming
procedure). It can also be triggered from the keypad, by means of the user function O
UTS
CONTROL
. The cut-off time programmed for the output should be longer than that required
for lowering the roll shutters.
The roller shutter "up" and "down" functions must be assigned to consecutive
(following each other) physical outputs.
If the 105. S
HUTTER UP
and 106. S
HUTTER DOWN
type outputs are to be controlled from
the keypad, they must be assigned to a group of outputs (see: section O
UTPUT GROUPS
p. 54).
For the 105. S
HUTTER UP
and 106. S
HUTTER DOWN
type outputs, indicate a partition so
that these outputs can be controlled from the keypad serving the given partition. If the
partition status is not to control the output status, enable the N
OT CONTROLLED BY
ARMING
option.
107. C
ARD ON READER
A
– indicates the proximity card / DALLAS iButton read-in by the
expander reader A. It can also signal card reading in the LCD keypad.
108. C
ARD ON READER
B
– indicates the proximity card / DALLAS iButton read-in by the
expander reader B. It can also signal card reading in the LCD keypad.
109. Z
ONES LOGICAL
AND
– active, when all zones selected as the control ones are violated.
110. A
LARM
–
NOT VERIFIED
– signals unverified alarms.
111. A
LARM
–
VERIFIED
– signals verified alarms.
112. V
ERIFIED
–
NO ALARM
– informs that the alarm has not been verified (during the alarm
verification no alarm was triggered by any other zone included in the verification).
113. V
ERIFICATION DISABLED STATUS
– signals disabling alarm verification.
114. Z
ONE TEST STATUS
– indicates the zone testing by means of user functions.