44 Programming
SATEL
Abort delay
– when this option is enabled, violating the zone during the entry delay
countdown will result in registering a "Zone violation" event (this event can only be
reported in the 4/2 format). When the option is disabled, violating the zone during the entry
delay countdown will result in registering an "Alarm" event (this event is reported and
initiates messaging).
Report if not armed
– option for the 7. D
AY
/N
IGHT
zone type. If it is enabled, the alarm will
be reported at all times. If it is disabled, the alarm will only be reported if the zone is
armed. If the zone is disarmed, the zone violation will trigger a warning alarm. The warning
alarm does not cause any loud alarm signal and is not reported. It can be signaled by the
9. DAY
A
LARM
, 12. S
ILENT ALARM
and 116. I
NTERNAL SIREN
type outputs.
Partition temporary blocking
– option for the 84. G
UARD
zone type. If it is enabled, violation
of the zone will block the partition for the time of guard round.
Restore after bell
– with this option enabled, the zone restore code will be reported to the
central monitoring station only after the alarm signaling is ended.
Restore after disarm
– with this option enabled, the zone restore code will be reported to
the central monitoring station only after disarming the partition to which the zone belongs.
Alarm on exit delay end
– with this option enabled, the zone will trigger alarm if it is violated
at the moment of ending the exit delay countdown. If the option is disabled, the alarm will
only be triggered in case of changing the zone status from normal to violated when armed.
Store to event log
– option for the 47. N
O ALARM ACTION
and 63. T
ROUBLE
zone types. If it is
enabled, violation of the zone will result in storing an event according to the zone type (in
case of the 47. N
O ALARM ACTION
zone type, the information to be written depends
additionally on the N
O REPORTING
option).
No reporting
– option for the 47. N
O ALARM ACTION
zone type with the S
TORE TO EVENT LOG
option enabled:
– enabled – violation of the zone will write an event informing about zone violation;
– disabled – violation of the zone will result in writing an event informing about keybox
opening, the code of which is sent to the monitoring station.
No restore event
– option for the 47. N
O ALARM ACTION
zone type with S
TORE TO EVENT LOG
and N
O REPORTING
options enabled. If it is enabled, the zone restore is not stored into the
event log.
Store event only if armed
– option for the 47. N
O ALARM ACTION
zone type. It is available, if
the S
TORE TO EVENT LOG
option is enabled. If it is enabled, violations of the zone will be
written into the event log, provided that the partition to which the zone is assigned, is
armed.
No bypass if armed
– option for the 64-79 zone types. If it is enabled, violation of the armed
zone will block no group of zones (provided that during the exit delay countdown an exit
from the partition is recorded).
Abort voice messaging
– option for the 81-83 zone types. If it is enabled, violation of the
zone will cancel the messaging, if it is currently ongoing.
Alarm on unbypass
– if the option is enabled and the armed zone is violated after being
bypassed, an alarm will be triggered.
Tamper alarm always loud
– if this option is enabled, tamper alarm is always loud (if option
is disabled – tamper alarm is loud only when armed).
Reporting delay
– option for the 4–7 and 64–79 zone types. Violation of the zone during the
entry delay countdown will trigger a warning alarm. The warning alarm does not cause any
loud alarm signal and is not reported. It can be signaled by the outputs of 9. DAY
A
LARM
,
12. S
ILENT ALARM
and 116. I
NTERNAL SIREN
type. If the zone is not disarmed within 30
seconds, the entry delay has expired or another instant is violated, the burglary alarm will
be triggered.