5-6
5
Remote
controller
alarm display
Alarm
contents
Judgement conditions
Eliminating
condition of alarm
Judgement and correction
P29
Error in current
detection circuit.
• AC current value
is high, even while
compressor is
halted.
• Inverter halted after alarm
detected.
• Alarm output on 4 consecutive
(pre-trips.)
Recovery at restart
1.Stops immediately even
when operations restarted.
• Layer short on the
compressor
2.Check HIC circuit
• Wiring trouble
F04
Disconnection, open
circuit or short circuit
in discharge
temperature sensor
(TD)
Sensor detection error (90
or more after 60 minutes has
elapsed since the compressor
was halted.)(Open circuit)
Automatic recovery
1.Check discharge temp.
sensor (TD).
2.Check outdoor unit control
PCB.
F06
Disconnection, open
circuit or short circuit
in outdoor unit heat
exchanger temp.
sensor (C1)
Open circuit or short circuit
Automatic recovery
1.Check outdoor unit heat
exchanger temperature
sensor (C1).
2.Check outdoor unit control
PCB.
F07
Disconnection, open
circuit or short circuit
in outdoor unit heat
exchanger temp.
sensor (C2)
Open circuit or short circuit
Automatic recovery
1.Check outdoor unit heat
exchanger temp. sensor
(C2).
2.Check outdoor unit control
PCB.
F08
Disconnection, open
circuit or short circuit
in outdoor air temp.
sensor (TO)
Open circuit or short circuit
Automatic recovery
1.Check outdoor air temp.
sensor (TO).
2.Check outdoor unit control
PCB.
F12
Disconnection, open
circuit or short circuit
in suction temp.
sensor (TS)
Open circuit or short circuit
Automatic recovery
1.Check suction temp. sensor
(TS).
2.Check outdoor unit control
PCB.
F31
EEPROM trouble
Reading/writing failure
Power reset recovery
1.Check EEPROM (IC007).
2.Check outdoor unit control
PCB.
L02
Indoor and outdoor
units incompatible
(PAC-i, ECO-i, GHP)
Indoor unit judged incompatible
with the outdoor unit type
Power reset recovery
1.Check indoor unit EEPROM.
2.Check indoor unit control
PCB.
L04
Settings failure
Duplicated outdoor unit address
(system address)
Automatic recovery
1.Check outdoor unit system
address.
2.Check inter-unit control
wiring.
L07
Settings failure
Group control wiring exists in
an individually-controlled indoor
unit.
Power reset recovery
1.Check inter-unit control
wiring.
2.Check indoor unit EEPROM.
L10
Settings failure
Outdoor unit capacity not set.
Power reset recovery
Check outdoor unit EEPROM.
L13
Indoor and outdoor
unit types
Outdoor unit judged incompatible
with the outdoor unit type
Automatic recovery
1.Check indoor unit EEPROM.
2.Check outdoor unit control
PCB.
E06
Outdoor unit detected
a signal error from
the indoor unit
Serial signals receiving failure
(including faulty unit quantity
confi rmation)
Automatic recovery
1.Check inter-unit control
wiring.
2.Check indoor and outdoor
unit control PCB.
E07
Outdoor unit sending
failure to indoor unit
Serial signal sending failure
Automatic recovery
1.Check inter-unit control
wiring.
2.Check outdoor unit control
PCB.
SM830160-03̲Classic̲PAC-i̲A4.ind6 6
SM830160-03̲Classic̲PAC-i̲A4.ind6 6
2010/02/16 10:30:05
2010/02/16 10:30:05
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...