1
1-323
This unit requires no additional refrigerant
charge up to tubing length 30 m. In case
of more than 30 m, additional refrigerant
charge is required. Refer to Tables 1-2
and 1-3.
In case of multi type installation, indoor
units should be installed within the
same room. If multi type indoor units are
installed in different rooms, temperature
control may develop problems because
thermostat operation must follow the
thermostat condition of 1 indoor unit only
(the main unit).
1.
2.
Always check the gas density
for the room in which the unit is
installed.
Check of limit density
When installing an air conditioner in a room, it is
necessary to ensure that even if the refrigerant gas
accidentally escapes, its density does not exceed the
limit level.
If the density might exceed the limit level, it is
necessary to set up an opening between it and the
adjacent room, or to install mechanical ventilation
which is interlocked with a leak detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where the indoor unit is installed: m3)
< Limit density 0.3 (kg/m
3
)
The limit density of refrigerant which is used in this
unit is 0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fi xed for each type, so add it
to the amount that is charged at the fi eld. (For the
refrigerant charge amount at shipment, refer to the
unit’s nameplate.)
Minimum indoor volume & fl oor area relative to the
amount of refrigerant are roughly as given in the
following table.
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can
collect, since refrigerant gas
is heavier than air.
CAUTION
WARNING
CAUTION
10
13.5
27.0
40.5
54.0
67.5
81.0
94.5
108
121.5
135
5
10
15
20
25
30
35
40
45
50
m
3
m
2
20
30
40 kg
Min. indoor fl
oor area
(when the ceiling is 2.7 m high)
Total amount of refrigerant
Range below
the density limit
of 0.3 kg/m
3
(countermeasures
not needed)
Range above
the density limit
of 0.3 kg/m
3
(countermeasures
needed)
Min. indoor volume
SM830160-03̲Classic̲PAC-i̲A4.ind323 323
SM830160-03̲Classic̲PAC-i̲A4.ind323 323
2010/02/16 10:26:49
2010/02/16 10:26:49
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...