2
2-29
2-31. Table of Self-Diagnostic Functions and Corrections (XM Type)
Wired remote
controller display
Indoor unit
receiver lamp
Cause
Correction
Group connection and simultaneous-operation
multi system
Nothing is displayed Nothing is displayed.
• Remote controller is not connected with indoor
unit correctly.
• Indoor unit power is not ON.
Connect the remote controller correctly.
Turn ON the indoor unit power.
E01
displayed
Operating lamp is
blinking.
• Automatic address setting has not been
completed.
• Inter-unit control wiring is cut or is not connected
correctly.
• Remote controller is not connected with indoor
unit correctly.
Check the remote controller and inter-unit
control wiring.
Perform automatic address setting (See 2-32).
E02
displayed
• Remote controller is not connected with indoor
unit correctly.
Connect the remote controller correctly.
E14
displayed
• Remote controller communication wiring is cut or
is not connected correctly.
Check the remote controller communication
wiring. Perform automatic address setting again.
E04
displayed
Standby lamp is
blinking.
• Indoor-outdoor inter-unit wiring is cut or is not
connected correctly.
Connect the wiring correctly.
E06
displayed
• Indoor-outdoor inter-unit wiring is cut or is not
connected correctly.
Refer to 2-32-1 System Control, and make the
correct settings.
E15
displayed
• Indoor unit capacity is too low.
Check that the total capacities of the indoor
and outdoor units are appropriate.
E16
displayed
• Indoor unit capacity is too high.
P05
displayed
Operation lamp and
Standby lamp are
blinking alternately.
• Reversed phase at one of the outdoor units in the
group.
• Insuffi cient gas
Check that the CT senscr is not disconnected,
and make sure it is inserted.
Fill up the gas appropriately.
P09
displayed
Timer lamp and
Standby lamp are
blinking alternately.
• Ceiling panel connector at one of the indoor units
in the group is not connected correctly.
Connect the indoor unit ceiling panel connector
correctly.
P12
displayed
• DC fan trouble at one of the indoor units in the
group.
Check whether the fan holder is loose.
Check the wiring between the DC fan and the
PCB.
L02
displayed
L13
displayed
Both the Operation
lamp and Standby
lamp are blinking
simultaneously.
• Indoor-outdoor unit type mismatch.
Check that the indoor and outdoor unit types
are correct.
L07
displayed
• Remote controller communication wiring is
connected to the indoor unit, however it is set for
individual operation.
Perform automatic address setting (See 2-32 ).
L10
displayed
• Check outdoor operation with separate maintenance-use remote controller.
SM830160-03̲Classic̲PAC-i̲A4.ind29 29
SM830160-03̲Classic̲PAC-i̲A4.ind29 29
2010/02/16 10:28:15
2010/02/16 10:28:15
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...