Installing Distribution Joint Kit (for Twin &
Double-Twin) (APR-P160BG)
Use a tube cutter and cut at the size position that
corresponds to the fi eld-supply tube size selected
based on the total indoor unit capacity. (If the size
is the same as the tube end size, cutting is not
necessary.)
If the reducer that was supplied in the package is
used, perform brazing on-site.
Do not cut in such a way that applies excessive
force and causes deformation of the tube. (This
will prevent insertion of the connecting tube.)
For size selection, refer to “Information for the
Person in Charge of Installation” and other
materials that were supplied with the outdoor
unit.
Cut at a position that is as far away as possible
from the dowel pin.
After cutting the tube, be sure to remove any burrs
and to fi nish the end surface correctly.
(If there is excessive crushing or indentation of the
tube, use a tube expander to expand it.)
Check that there is no dirt or other foreign
substance inside the distribution tubing.
Install the distribution tubing so that it is either
horizontal or vertical.
Use the supplied thermal insulation to insulate the
distribution tubing.
(If other insulation is used, be sure to use insulation
that can withstand temperatures of at least 120° C.)
For details, refer to “Information for the Person in
Charge of Installation”.
Nitrogen gas replacement required for tube
brazing
If nitrogen replacement is not done when brazing is
performed on the indoor and outdoor unit refrigerant
tubing, oxide scale will occur. This scale will clog the
solenoid valves, strainers, and other parts, leading to
malfunction.
Therefore be sure to replace the air in the tubing with
nitrogen when performing brazing in order to prevent
problems from oxide scale.
•
•
•
•
•
•
•
•
NOTE
If the distribution joint will be cut before use, cut on the
line marked “cutting point” in the fi gure below.
Stopper (boss)
Cutting point
Make this as long as possible.
Insertion length of the connecting tube
Horizontal installation
Outdoor unit
Side
Indoor unit
Side
15° to 30°
upward slant
Vertical installation (directed upward or downward)
SM830160-03̲Classic̲PAC-i̲A4.ind325 325
SM830160-03̲Classic̲PAC-i̲A4.ind325 325
2010/02/16 10:26:50
2010/02/16 10:26:50
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...