7
Item code
Item
Description
10
Unit type
Set when the indoor unit EEPROM memory is replaced during servicing.
11
Indoor unit capacity
12
System (outdoor unit)
address
These are not set at the time of shipping from the factory.
These must be set after installation if automatic address setting is not
performed.
13
Indoor unit address
14
Group address
17
Cooling intake
temperature shift
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.)
Increase this value when it is difficult to turn the thermostat ON.
18
Automatic stop time after
operation start
The time at which an indoor unit is automatically stopped after operation
starts can be set in increments of 5 minutes
1b
Forced thermostat ON
time
Use this setting to change the time for forced operation at installation
or servicing from 5 minutes to 4 minutes.
(Enabled only with PAC-i models.)
1C
Cooling discharge
temperature shift
Shifts the set value for models which perform discharge temperature
control.
(Discharge temperature control models: Floor discharge, wall built-in,
direct expansion coil outdoor air treatment, high-fresh)
1d
Heating discharge
temperature shift
1E
Temperature shift for
cooling/heating change in
“auto heat/cool” mode
“Auto heat/cool” selects the operating mode automatically based on the
difference between the room temperature and the temperature set on
the remote controller. This setting establishes a shift temperature for
the heating/cooling temperature setting relative to the remote controller
temperature setting.
Cooling temperature setting
Heating temperature setting
Remote controller temperature setting
Shift temperature
Shift temperature
7-6. Detaild Setting Items
7-12
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
2010/02/16 10:30:51
2010/02/16 10:30:51
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...