2-15. Table of Self-Diagnostic Functions and Corrections (K Type)
Wired remote
controller
display
(Field supply)
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (Single type)
Group connection
(Simultaneous
multi system)
Nothing is
displayed
Nothing is
displayed.
• Indoor operation switch is OFF.
• Indoor unit power is not ON.
• Same at left.
• Set the indoor operation switch ON.
• Turn ON the indoor unit power.
E01
displayed
Operating lamp
is blinking.
• Automatic address setting has not
been completed.
• Inter-unit control wiring is cut or is not
connected correctly.
• Same at left.
• Check the inter-unit control wiring.
• Perform automatic address setting. (See
2-16.)
E14
displayed
—
• Remote controller
communication
wiring is cut or is not
connected correctly.
• Check the remote controller
communication wiring.
• Perform automatic address setting again.
E04
displayed
Standby lamp is
blinking.
• Indoor-outdoor inter-unit wiring is not
connected correctly.
• Same at left.
• Connect the wiring correctly.
E06
displayed
—
• Inter-unit control
wiring is cut or is not
connected correctly.
• Refer to 2-16 System Control, and make
the correct settings.
E15
displayed
• Indoor unit capacity is too low.
• Same at left.
• Check that the total capacities of the
indoor and outdoor units are appropriate.
E16
displayed
• Indoor unit capacity is too high.
• Same at left.
• Reverse 2 phases of the outdoor unit
3-phase power and connect them
correctly.
P05
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
• Same at left.
• Connect the units correctly.
L02
displayed
Both the
Operation lamp
and Standby
lamp are blinking
simultaneously.
• Indoor-outdoor unit type mismatch.
• Same at left.
• Connect the units correctly.
L13
displayed
• Indoor-outdoor units are not setting
correctly.
• Same at left.
• Connect the units correctly.
L04
displayed
—
• Outdoor unit address
is duplicated.
• Connect the units correctly.
L07
displayed
—
• Remote controller
communication wiring
is connected to the
indoor unit, however,
it is set for individual
operation.
• Perform automatic address setting. (See
2-16.)
P15
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• No gas
• Same at left.
• Check the refrigerant cycle (for gas
leaks).
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
2010/02/16 10:28:10
2010/02/16 10:28:10
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...