8
8-17. RCS-SH80BG.WL
1. Accessories
No.
Accessories
Quantity
1
Receiver
1
2
Remote controller
1
3
Remote control holder
1
No.
Accessories
Quantity
4
AAA alkaline batteries
2
5
Users Manual
1
6
Truss self-tapping screws
4 X 16
2
7
Cable clamp
1
8
Clamp fi xing screw 4 X 12
1
2. Installing the Receiver Unit
The receiver can only be installed on the corner indicated in Fig. 8-1, so consider how the panel will face when it is
installed on the indoor unit.
(1) Remove the air inlet grill.
(2) Remove the screw holding the adjustable corner cap, slide the cap to the side and remove it. (Fig. 8-2)
(3) A packing is stuffed into the square hole through which the panel wiring passes; temporarily remove the sponge
packing and pass the wire sticking out from the wireless receiver through the grill. Hold the wire in place with
the enclosed clamp by tightening the screw, then stuff the sponge back in place. (Fig. 8-3)
If this packing is not put back, condensation may form on the wire, so it is absolutely necessary to put the
sponge packing back in place before continuing with the installation.
(4) After wiring according to the directions in Wiring the Receiver Unit on the next page, leave enough wiring so the
receiver’s adjustable corner cap can be removed and fasten the cable clamp with its screw. (Fig. 8-3)
(5) Install the panel on the receiver. When doing so, slide the panel so its tabs fi t into their 3 places. Also, take care
so the wire does not get pinched. (Fig. 8-4)
• Refer to the Installation Manual packed with the panel.
NOTE
(1) If the wiring for the receiver is bundled with other wires, such as the incoming line, it may cause a malfunction,
so avoid putting them together.
(2) If something causes the unit’s power source to make noise it will be necessary to resolve the problem, such as
by installing a noise fi lter.
• For more information about wiring or test operation, refer to Wiring the Receiver Unit and Test Operation on the
next page.
Receiver installation
Location
Box with Indoor
Unit’s Electrical
Parts
Adjustable Corner Cap
Ceiling Panel
Adjustable Corner Cap
Remove the sponge packing, fasten the wire
with the cable clamp and put the sponge
packing back in place.
Screw
8-12
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
SM830160-03̲Classic̲PAC-i̲A4.ind12 12
2010/02/16 10:31:19
2010/02/16 10:31:19
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...