5-4
5
5-2. Contents of LED Display on the Outdoor Unit Control PCB
LED 1
LED 2
Remarks
Power ON sequence
1. No communication from indoor units in system
2. Communication received from 1 or more indoor units in system
3. Regular communication OK (Capacity and unit quantity match)
If it is not possible to advance to 3,
repeats 1 2.
At 3, changes to normal control.
Normal operation
Displayed during automatic address
setting 1 and initial communication.
After these are completed, alarm F31 is
displayed.
EEPROM error (F31)
Pre-trip (insuffi cient gas)
Pre-trip (P20)
Pre-trip (other)
(0.25/0.75)
(0.75/0.25)
P03
Alarm
Alternate blinking during alarms
LED 1 blinks M times, and then LED 2 blinks N times.
The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
* Refer to “Examples of alarm display” below.
Insuffi cient gas indicator
Refrigerant recovery mode
Automatic address setting
Automatic address setting in progress
Automatic address setting alarm (E15)
Automatic address setting alarm (E20)
Automatic address setting alarm (Other than E15 and E20)
(0.25/0.75)
(0.75/0.25)
(0.25/0.75)
(0.75/0.25)
Blinking alternately
Blinking simultaneously
Blinking simultaneously
Blinking simultaneously
:
ON
:
Blinking (0.25/0.75)
indicates that the lamp illuminates for 0.25 seconds, and then is OFF for 0.75 seconds.
Unless otherwise indicated, the blinking is (0.5/0.5).
:
OFF
Examples of alarm display (other than E15, E16, and E20)
Alarm / Display
LED 1
Alternately
LED 2
P02
( Blinks 2 times )
(Blinks 2 times)
P03
( " )
(Blinks 3 times)
P04
( " )
(Blinks 4 times)
P05
( " )
(Blinks 5 times)
P31
( " )
(Blinks 31 times)
H01
(Blinks 3 times)
(Blinks 1 times)
H02
( " )
(Blinks 2 times)
H03
( " )
(Blinks 3 times)
•
•
E04
(Blinks 4 times)
(Blinks 4 times)
•
•
F07
(Blinks 5 times)
(Blinks 7 times)
•
•
L13
(Blinks 6 times)
(Blinks 13 times)
•
•
Note:
This table shows examples of alarms.
Other type of alarms may also be displayed.
SM830160-03̲Classic̲PAC-i̲A4.ind4 4
SM830160-03̲Classic̲PAC-i̲A4.ind4 4
2010/02/16 10:30:04
2010/02/16 10:30:04
Summary of Contents for SPW-C256VH
Page 364: ... MEMO 1 358 ...
Page 398: ... MEMO 2 34 ...
Page 404: ...3 6 3 3 1 Indoor Units Wall Mounted Type SPW KR124GH56 SPW KR184GH56 Schematic Diagram 䡵 ...
Page 405: ...3 7 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Electric Wiring Diagram 䡵 ...
Page 406: ...3 8 3 3 1 Indoor Units Wall Mounted Type SPW KR254GH56 Schematic Diagram 䡵 ...
Page 415: ...3 17 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Electric Wiring Diagram 䡵 ...
Page 416: ...3 18 3 3 1 Indoor Units Concealed Duct Type SPW US125 165 185H Schematic Diagram 䡵 ...
Page 417: ...3 19 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256VH ...
Page 419: ...3 21 3 3 2 Outdoor Units Electric Wiring Diagram SPW C366VH ...
Page 421: ...3 23 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486VH ...
Page 423: ...3 25 3 3 2 Outdoor Units Electric Wiring Diagram SPW C256 366VH8 ...
Page 425: ...3 27 3 3 2 Outdoor Units Electric Wiring Diagram SPW C486 606VH8 ...
Page 472: ... MEMO 6 10 ...
Page 490: ... MEMO 7 18 ...
Page 517: ...SANYO Electric Co Ltd Printed in Japan 201002E DC ...