MOUNTING METHOD 1: UNI-STRUT
5.1 Select Proper Unistrut:
NOTE: Unistrut and Unistrut hardware is not included with the fan. This equipment must be field supplied.
(2) 1-5/8” Unistrut Channels (
not provided
).
If the spanning distance is greater than 8 feet, please consult a structural engineer.
Span two (2) pieces of 1-5/8” Unistrut open side facing down and space apart so there is 12-7/8” from outside
edge to outside edge.
Once the Unistrut is in place, apply liquid thread lock to the recommended bolts and use the remaining
recommended hardware to attach the mount to the Unistrut.
Follow the table below when selecting Unistrut for fan installation. PLEASE NOTE: These are recommendations. S&P
is not liable for accidents resulting from improperly sized mounting methods. Please consult a structural engineer.
Support Directly From Building Structure.
All mounting instructions assume that the building structure from which the fan will be hung is of sound
construction, undamaged, and capable of supporting loads of up to 650 lbs (295 kg). It is the sole
responsibility of the customer to verify that the building’s structure is adequate for fan installation. S&P
recommends consulting with a structural engineer prior to fan installation.
Aider directement à la structure du bâtiment.
Toutes les instructions de montage supposent que la structure du bâtiment à partir de laquelle le ventilateur sera pendu
est de construction solide, en bon état, et capable de supporter des charges de jusqu’à 650 lb (295 kg). Il est de la
seule responsabilité du client de vérifier que la structure du bâtiment est suffisante pour l’installation du ventilateur. S&P
recommande de consulter un ingénieur en structure avant d’attiser installation.
WARNING/ AVERTISSEMENT
Unistrut Span
(between
mounting point)
Minimum
Unistrut Size
(W x H x T)
Qty. of
Unistrut
Needed
< 8’ (2.4m)
1-5/8”
2