8
3
MOUNTING CONSIDERATIONS
3.1 General Mounting
Each type of mounting system requires a specific mounting bracket. Most are available from S&P. Check with
the contractor, building owner, or architect to ensure the structure is sound and will support the weight of the fan
before beginning installation. S&P provides guidelines for mounting fans; however, it is the sole responsibility of the
building owner and installer to ensure the safety of the mounting system, that the building structure is sound, and the
installation complies with all federal, state, and local codes.
3.2 Weight
A Standard 1.35-horsepower, Tempest Fan 16 foot 6-blade fan and mounting assembly weighs about 155 pounds.
In inverted-blade applications designed to blow air upward, there is an additional downward force of about 80
pounds due to fan thrust. We recommend applying a safety factor of 2 times the stated hanging weight of the fan
when determining the capabilities of the building structure.
3.3 Safety Cable
A S&P fan should never be run without proper installation of Safety Cables. These are supplied with every fan. You
must install safety cable for warranty to be in effect.
3.4 Guy Wires
While in operation a fan can sway due to minor imbalance or because of wind. Since the mounting system is
capable of swiveling, it will not stop fan movement, so it is important that the guy wires be installed properly. Proper
installation includes the angle and tension of the guy wires. See page 22-23 for more information.
3.5 Universal Mounting Hardware
We recommend mounting the fan to a horizontal structural beam, however, this is not always possible in buildings
with pitched roof construction. For this reason, our universal mounting system is designed to allow the fan to hang in a
level position perpendicular to the ground by rotating the upper yoke 90 degrees.
When cutting or drilling into a wall or ceiling, take care not to damage electrical wiring or other utilities.
Lorsque vous coupez ou percez un mur ou un plafond, prenez garde à ne pas endommager les fils électriques ou
d’autres services publics.
Select a location that is free from obstructions that may interfere with the fan’s operation.
Choisissez un emplacement qui est libre de tout obstacle pouvant interférer avec le fonctionnement du ventilateur.
CAUTION/ATTENTION