59
8-06
Speed tracking time for B.B
Factory setting
d 0.5
Setting range
d 0.3<->d 5.0S
Unit
0.1S
If power supply interruption is detected, AC motor drive shall stop output and shall not be re-started
until after set time by this parameter. It’s preferred to provide output side residual voltage to be
approximately 0V prior to AC motor drive starting.
When setting external B.B and restart after fault, this parameter shall be time for speed tracking.
8-07
Max current setting for speed tracking
Factory setting
d 150
Setting range
d 30<->d 200%
Unit
1%
可允许停电之最长时间
Max allowable time for power loss
输入电源
Input power supply
输出频率
Output frequency
速度寻找
speed search
输出电压
Output voltage
变频器由停电前速度往下追踪
Track downwards from speed before power loss of inverter
B.B
时间
B.B time
速度同步检测
speed synchronous detection
变频器由停电前速度往上追踪
Track upwards from speed before power loss of inverter
8-08
Max of inhibited frequency setting 1
Factory setting
d 0.0
8-09
Min of inhibited frequency setting 1
Factory setting
d 0.0
8-10
Max of inhibited frequency setting 2
Factory setting
d 0.0
8-11
Min of inhibited frequency setting 2
Factory setting
d 0.0
8-12
Max of inhibited frequency setting 3
Factory setting
d 0.0
8-13
Min of inhibited frequency setting 3
Factory setting
d 0.0
Setting range
d 0.0<->d 400Hz
Unit
0.1Hz
Parameters above define inhibited frequency setting, and this range shall be avoided from
frequency setting for AC motor drive, reason is that frequency output shall not be stable at these
ranges but shall stay beyond these ranges of frequency. However, since frequency output shall be
continuous, when frequency is not set within these ranges, frequency output shall be continuous
and jumping shall not occur at locations of inhibition frequency.
8-14
Fault restarting times
Factory setting
d 0
Setting range
d 0<->d 10
Times of auto restarting of AC motor drive shall be set to 10 times after fault (for fault allowable
situations: OC (over current) and OV (over voltage)). If it is set to 0, auto-reset/restarting function
shall not be performed. In restarting after fault, AC motor drive shall be started in speed tracking
mode up to down.