33
0-01
Rated current of AC motor drive (Only for reading)
Factory setting
d#.#
Setting range
Non
This parameter displays the rated current of AC motor drive, corresponding to machine types
displayed at Parameter 0-00.
0-02
Parameter resetting
Factory setting
d 0
Setting range
d 0~20 No action
d 10
All parameters reset to factory setting
Resetting all parameters to factory setting shall be available by this parameter.
0-03
Machine On display Selection
Factory setting
d 0
Setting range
d 0
F (Displaying set frequency reference)
d 1
H(Displaying actual running frequency)
d 2
U(Displaying multifunctional definitions )
d 3
A( displaying motor running current)
This parameter enables users to determine the machine ON display by themselves.
0-04
Determining multifunctional display
Factory setting
d 0
Setting range
d 0
Displaying output physical quantity(u) defined by operators
d 1
Displaying count value (c)
d 2
Displaying program operation content (X=tt)
d 3
Displaying DC-BUS voltage(U)
d 4
Displaying output voltage (E)
d 5
Displaying rotating speed(R )
d 6
Output frequency 2 (after slip compensation) (h)
d 7
Consumed power (p)
Output physical quantity defined by users shall be displayed when it is set to 0 (Physical quantity
=H×0-05)
0-05
Proportional constant setting
Factory setting
d 1.0
Setting range
d 0.1<->d 160
Unit
0.1
Proportional constant, the constant used in output physical quantity defined by users. This
parameter should be used in conjunction with d0, d5 and d6 of 0-04.
The display value shall be counted as this formula shows:
When set 0-04 as 0, display value= Output frequency (
before slip compensation
) x K (0-05)
When set 0-04 as 5, display value= rotating speed x K (0-05)
When set 0-04 as 6, display value= Output frequency 2 (
after slip compensation
) x K (0-05)
0-06
Software Version
Factory setting
d #.##
Setting range Non
Software version is only for reading.