22
1 Basic Parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
1-00
Max operation frequency setting
5.0~400Hz
50.0
1-01
Max voltage frequency setting
10.0~400.0Hz
50.0
1-02
Max output voltage setting
220V:2.0~255.0V
220
440V:2.0~510V
440
1-03
Intermediate frequency setting
0.1~400Hz
1.0
1-04
Intermediate voltage setting*
220V:2.0~255V
12.0
440V:2.0~510V
24.0
1-05
Min output frequency setting
0.1~60.0Hz
1.0
1-06
Min output voltage settubg*
220V:2.0~255V
12.0
440V:2.0~510V
24.0
1-07
Max frequency of output frequency
1~110%
100
1-08
Min frequency of output frequency
0~100%
0
1-09
1st Acceleration time
0.01~600s
10.00
1-10
1st Deceleration time
0.01~600s
10.00
1-11
2nd acceleration time
0.01~600s
10.00
1-12
2nd deceleration time
0.01~600s
10.00
1-13
JOG acceleration time setting
0.01~600s
10.00
1-14
JOG deceleration time setting
0.01~600s
10.00
1-15
JOG frequency setting
1.0~400Hz
6.0
1-16
Reserved
1-17
Reserved
1-18
Reserved
1-19
V/f curve setting
0~6
0
2 Operation mode parameters Set during running available
Parameter
Parameter functions
Setting range
Factory setting
2-00
Master frequency input
source
0: Keyboard(OP) input
3
1: Input DC 0 to 10V by external terminals AVI
2: Input 4 to 20Ma by external terminals ACI
3: controlled by VR on digital controller
4:Operated by RS-485 communication
interface
5:Operated by RS-485 communication
interface(Frequency memory)
6:Controlled by UP/DOWN
7:Controlled by UP/DOWN (Frequency
memory)
8:
Reserved