39
2-03
Operation Reference Source
Factory setting
d 0
Setting
range
d 0
0: Operated by keyboard
d 1
1: Operated by external terminals. STOP on keyboard available
d 2
2: Operated by external terminals. STOP on keyboard unavailable
d 3
3: Operated by Communication Interface RS-485. STOP on keyboard available
d 4
4: Operated by Communication Interface RS-485. STOP on keyboard
unavailable
For external operation source reference, apart from parameter 2-03 shall be set, others see detailed
descriptions in Parameter Group 4.
2-04
STOP mode
Factory setting
d 0
Setting
range
d 0
0: Deceleration and stop
d 1
1: Coast to a stop
After STOP reference received, the AC motor drive shall control the motor to stop as parameter set.
Deceleration and stop: according to deceleration time set by 1-10 or 1-12, AC motor drive
decelerate in tape speed way to min output frequency(1-05) and then machine stops.
Coast to a stop: AC motor drive stops output immediately and motor runs freely in load inertia and
then stops.
1 Deceleration and stops 2. Free running
The motor stopping mode depends on the characteristics of load or machinery stopping
It’s recommended to choose the mode of deceleration and stop in circumstance that, when
machines stops, motor shall stop immediately to avoid individual injury or waste of materials.
However, deceleration time shall be determined according to specific characteristics of machine.
While it shall be set to free running and stops, provided motor idling allowable or machine with large
load flexibility, for example, air fan, pump and stirring machines.
2-05
Reserved
SET FREQUENCY
MOTER SPEED
OPERATION REFERENCE
DECELERATION TIME
MOTER SPEED
SET FREQUENCY
DECELERATION TIME
Motor stops
with 1
st
deceleration time
1-10/ 2
nd
deceleration time
1-12 set by Parameter
Motor runs freely in load inertia and then stops
time
time