71
A Wobble Frequency Function Parameters
Wobble function shall be applicable to industries such as textile and chemical fiber, and circumstances
which needs traversing or coiling. Diagram below shows typical work diagram:
运行频率
Running frequency
摆频上限频率
Max wobble frequency
中心频率
Centering frequency
摆频下限频率
Min wobble frequency
摆 频 预 置 频 率
Wobble preset
frequency
摆频幅度
wobble amplitude
纺 织 突 跳 频 率
Textile hopping
frequency
按 加 速 时 间 加 速
Accelerate in
accordance with acceleration time
纺织起动等待时间
waiting time for
textile starting
三角波上升时间
triangle wave rising
time
摆频周期
wobble frequency cycle
按 减 速 时 间 减 速
Decelerate in
accordance with deceleration time
时间
time
运行命令
Running command
停机命令
machine stop command
Wobble process shall be following for general: Firstly accelerate in accordance with acceleration time to
preset frequency A-02, and wait for a time of A3, then wobble centering frequency (A-04, A-05)
according to accel/decel time shall be realized. After that, it shall run in cycle in set wobble amplitude
(A-06, A-07), wobble frequency hopping A-08, wobble cycle A-09 and triangle wave rising frequency
A-10. It shall stop in accordance with deceleration time when a STOP command is received.
Also attention shall be paid that, wobble frequency shall be cancelled automatically in jog running or
closed loop running.
PLC shall run simultaneously with wobble frequency, and wobble frequency shall be unavailable in
switching of Plc period. Wobble frequency shall start after PLC setting is reached in accordance with
accel/decel setting in Plc period; and decelerating to machine stop shall be according to deceleration
time in PLC step.
A-00
Wobble Frequency Function selection
Factory setting
d 0
Setting range
d 0
Not using wobble function
d 1
Using wobble function
This parameter is to determine using wobble frequency function or not.
A-01
Wobble Frequency input mode
Factory setting
d 0
Setting range
d 0
Input automatically (A-03)
d 1
Manually controlled by external terminals.
This parameter is to set input mode of wobble frequency:
When it is set to 0, it shall be input automatically. In this case, it shall firstly run for a period (A-03) in
wobble frequency preset frequency (A-02) after starting, and then wobble frequency shall be
realized automatically.
When it is set to 1, it shall be controlled manually by external terminals. Which means that wobble
frequency shall be realized when multifunction terminal (Function 27 is for wobble frequency input)
available; while wobble frequency shall not exist when terminal unavailable, with running frequency
kept at wobble frequency preset frequency A-02.