Piping Diagram
Samsung Electronics
277
High-head condition setting
▪
Purpose
Secure performance and reliability when using units installed under a high-head condition.
▪
Concept
-
Control of the compressor frequency, outdoor fans, EEV, and valves is optimized to facilitate the circulation of
refrigerant in any head condition.
▪
Control specifications in detail
- In Type 1 heating mode, the initial EEV opening degree increases.
The compressor frequency increase speed decreases if the low pressure is low
(see "Main EEV control" for details on EEV control).
- In Type 2 heating mode, the initial EEV opening degree decreases.
The compressor frequency increase speed decreases if the low pressure is low
(see "Main EEV control" for details on EEV control).
- In Type 2 cooling mode, the target high pressure for outdoor fans increases to 28kgf/cm2,g.
(see "Fan control" for details on controlling outdoor fans).
- In Type 1 and 2 cooling modes, EVI bypass mode turns on (see "EVI EEV control" for details).
▪
Notes
- Incorrect settings may damage the system.
Input unit
Seg1
Seg2
Seg3
Seg4
Silent mode for night - time
Main
0
8
0
0
Disabled (default)
0
1
Level 1 of Type1
(When outdoor unit is located 40~80m
above the indoor unit)
0
2
Level 2 of Type 1
(When outdoor unit is located over 80m
above the indoor unit)
0
3
Type 2
(When indoor unit is over 30m above the outdoor unit)
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)