Troubleshooting
4-2 Service Operation
4-2-1 Special Operation (cont.)
K4
(Number of press)
Press and hold the K4 to
enter the setting
Displayed content
Display on segment
PAGE1
PAGE2
1 time
Main version
MAIN
Version (ex. 1412)
2 times
Hub version
HUB
Version (ex. 1412)
3 times
Inverter 1 version
INV1
Version (ex. 1412)
4 times
Inverter 2 version
INV2
Version (ex. 1412)
5 times
Fan 1 version
FAN1
Version (ex. 1412)
6 times
Fan 2 version
FAN2
Version (ex. 1412)
7 times
EEP version
EEP
Version (ex. 1412)
8 times
Automatically assigned address of the units
AUTO
SEG1
SEG2
SEG3,4
Indoor unit: “A” MCU:
“C”
Indoor unit: “0”
MCU: “1”
Address
(ex: 07)
9 times
Manually assigned address of the units
MANU
SEG1
SEG2
SEG3,4
Indoor unit: “A”
Indoor unit: “0”
Address (ex: 15)
※ I/U : Indoor unit
K4
(Number of press)
KEY operation
Display on segment
SEG1
SEG2, 3, 4
9 times
IPM temperature (Compressor 2)
9
87 °C
→
0, 8, 7
10 times
CT sensor value (Compressor 1)
A
2 A
→
0, 2, 0
11 times
CT sensor value (Compressor 2)
B
2 A
→
0, 2, 0
12 times
Suction temperature
C
-42 °C
→
-, 4, 2
13 times
COND OUT temperature
D
-42 °C
→
-, 4, 2
14 times
Temperature of liquid pipe
E
-42 °C
→
-, 4, 2
15 times
TOP temperature (Compressor 1)
F
-42 °C
→
-, 4, 2
16 times
TOP temperature (Compressor 2)
G
-42 °C
→
-, 4, 2
17 times
Outdoor temperature
H
-42 °C
→
-, 4, 2
18 times
EVI inlet temperature
I
-42 °C
→
-, 4, 2
19 times
EVI outlet temperature
J
-42 °C
→
-, 4, 2
20 times
Main EEV1 step
K
2000 steps
→
2, 0, 0
21 times
Main EEV2 step
L
2000 steps
→
2, 0, 0
22 times
EVI EEV step
M
300 steps
→
3, 0, 0
23 times
HR EEV step
N
300 steps
→
3, 0, 0
24 times
Fan step (SSR or BLDC)
O
13 steps
→
0, 1, 3
25 times
Current frequency (Compressor 1)
P
120 Hz
→
1,2,0
26 times
Current frequency (Compressor 2)
Q
120 Hz
→
1,2,0
27 times
Suction 2 temperature (HR Only)
R
-42 °C
→
-, 4, 2
28 times
Master indoor unit address
S
Main indoor unit not selected
→
BLANK, N, D
If indoor unit No 1 is selected as the main unit
→
0, 0, 1
29 times
Suction 3 temperature
U
-42℃→ -,4,2
30 times
COND OUT2 temperature
V
-42℃→ -,4,2