Product Specifications
Samsung Electronics
18
2-5-1 Outdoor Unit
■ DVM S2 HR(208~230V)
(cont.)
2-5 Product Specification(cont.)
Type
DVM S2 HR - 208-230V
Model CODE
AM072BXVGFR/AA
AM096BXVGFR/AA
AM120BXVGFR/AA
AM144BXVGFR/AA
AM168BXVGFR/AA
AM192BXVGFR/AA
AM216BXVGFR/AA
AM240BXVGFR/AA
Piping
Connections
Liquid Pipe
Φ, mm(inch)
9.52 (3/8")
9.52 (3/8")
12.7 (1/2")
12.7 (1/2")
15.88 (5/8")
15.88 (5/8")
15.88 (5/8")
15.88 (5/8")
Type
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Gas Pipe
Φ, mm(inch)
19.05 (3/4")
22.22 (7/8")
28.58 (1 1/8")
28.58 (1 1/8")
28.58 (1 1/8")
28.58 (1 1/8")
28.58 (1 1/8")
34.92 (1 3/8")
Type
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Discharge Gas Pipe
Φ, mm(inch)
15.88 (5/8")
19.05 (3/4")
19.05 (3/4")
22.22 (7/8")
22.22 (7/8")
28.58 (1 1/8")
28.58 (1 1/8")
28.58 (1 1/8")
Type
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Braze Connection
Heat Insulation
-
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Installation Limitation
Max. Length
m
220
220
220
220
220
220
220
220
Max. Height
m
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
50(110)/40(110)
Piping length (ODU-IDU)
Max. [Equiv.]
m
200 [220]
200 [220]
200 [220]
200 [220]
200 [220]
200 [220]
200 [220]
200 [220]
Piping length (1st Branch-IDU)
Max.
m
90
90
90
90
90
90
90
90
Total piping length (System)
Max.
m
1,000
1,000
1,000
1,000
1,000
1,000
1,000
1,000
Level difference (ODU in high-
est position)
Max.
m
110
110
110
110
110
110
110
110
Level difference (IDU in highest
position)
Max.
m
110
110
110
110
110
110
110
110
Level difference (IDU-IDU)
Max.
m
40
40
40
40
40
40
40
40
Field
Wiring
Power Source Wire
mm2
-
-
-
-
-
-
-
-
Transmission Cable
Min.
mm2
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
Transmission Cable
Remark
-
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
F1, F2
Power supply intake
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Both IDU&ODU
Refrigerant
Type
-
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Factory Charging
kg
6.2
8.0
8.0
10.5
10.5
12.5
15.5
15.5
lbs
13.7
17.6
17.6
23.1
23.1
27.6
34.2
34.2
External
Dimension
Net Weight
kg
179
257
257
276
299
380
389
389
lbs
395
567
567
608
659
838
858
858
Shipping Weight
kg
193
274
274
293
316
406
415
415
lbs
425
604
604
646
697
896
915
915
Net Dimensions (WxHxD)
mm
930x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
1295x1695x765
1860x1695x765
1860x1695x765
1860x1695x765
inch
36-5/8 x 66-3/4 x 30-1/8
51 x 66-3/4 x 30-1/8
51 x 66-3/4 x 30-1/8
51 x 66-3/4 x 30-1/8
51 x 66-3/4 x 30-1/8
73-1/4 x 66-3/4 x 30-1/8 73-1/4 x 66-3/4 x 30-1/8 73-1/4 x 66-3/4 x 30-1/8
Shipping Dimensions (WxHxD)
mm
998x1887x829
1363x1887x829
1363x1887x829
1363x1887x829
1363x1887x829
1928x1887x829
1928x1887x829
1928x1887x829
inch
39-5/16 x 74-5/16 x 32-5/8 53-11/16 x 74-5/16 x 32-5/853-11/16 x 74-5/16 x 32-5/853-11/16 x 74-5/16 x 32-5/853-11/16 x 74-5/16 x 32-5/8 75-7/8 x 74-5/16 x 32-5/8 75-7/8 x 74-5/16 x 32-5/8 75-7/8 x 74-5/16 x 32-5/8
Operating
Temp. Range
Cooling
℃
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
-15 ~ 50 ※1
℉
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
5.0 ~ 122.0 ※1
Heating
℃
-30 ~ 24
-30 ~ 24
-30 ~ 24
-30 ~ 24
-30 ~ 24
-30 ~ 24
-30 ~ 24
-30 ~ 24
℉
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
-22.0 ~ 75.0
※ 1: In order to operate cooling under the installation conditions specified in the installation manual (outdoor temperature below minus 5 degrees Celsius), a separate windproof guard must be installed on the suction side of the heat exchanger and at least 50% of the installed indoor
units must be operated. However, if the outdoor unit is installed below the indoor unit, cooling operation is possible only at 5 degrees or higher. ) It is a possible condition when satisfied, and if the condition is not satisfied, the temperature range is -5°C to 50°C.