Piping Diagram
Samsung Electronics
241
Main heating operation
▪
Purpose
Switch to cooling mode on some indoor units while using heating mode.
▪
Control specifications in detail
Actuator
-
Main Heating
Compressor
COMP
Operation
Target high pressure control
(default : 30kgf/cm2,g)
Range
20-160Hz
Outdoor Fan Motor
OFM
Operation
Target low pressure control
(default : 7.5-8.7kgf/cm2,g)
Range
0-39step (0-1300rpm)
Electronic Expansion Valve – Main (Main EEV)
E_M
Operation
*Superheat control
(default: SH 2 K)
Range
125-2000step
Electronic Expansion Valve – EVI (EVI EEV)
E_EVI
Operation
* EVI Superheat control
(default: SH 2 K)
Range
0-480step
Solenoid Valve - 4way
V_4W
Operation
On
Solenoid Valve – EVI Bypass
V_EB
Operation
On (Open):
T_a > 15
℃
or 50Hz
↓
Off (Close):
T_a < 10
℃
and 70Hz
↑
Solenoid Valve – EVI
V_EVI
Operation
On (Open)
Solenoid Valve – Hot Gas Bypass
V_HG
Operation
Off (Close)
Solenoid Valve – Accumulator Oil Return
V_AR
Operation
On (Open)
Solenoid Valve – Hot Gas Bypass 2 (HR Only)
V_HG2
Operation
Off (Close)
Solenoid Valve – Main EEV (HR Only)
V_ME
Operation
Off (Close)
Solenoid Valve – Main Cooling (HR Only)
V_MC
Operation
Off (Close)
7-3 Functions (cont.)
7-3-2-3 Normal operation modes (cont.)
7-3-2 Control (cont.)