Samsung Electronics
272
Piping Diagram
Heating capacity correction
▪
Purpose
Control the heating performance.
▪
Concept
The Target high pressure is changed to control the pressure in heating mode.
▪
Control specifications in detail
-
The high pressure for outdoor units and the compressor operation frequency are controlled according to the Target high
pressure that was configured in cooling mode.
- See "Compressor capacity control" for details on compressor operation specifications.
▪
Notes
-
When low pressure value is set, discharged air temperature of the indoor unit will decrease and power of
outdoor will increase.
Input unit
Seg1
Seg2
Seg3
Seg4
Pressure(kgf/cm2,g)
Main
0
2
0
0
30 (default)
0
1
25
0
2
26
0
3
27
0
4
28
0
5
29
0
6
31
0
7
32
0
8
33
7-3 Functions (cont.)
7-3-3-1 Field Setting (cont.)
7-3-3 Others (cont.)